2 Parameters
2.2 List of parameters
SINAMICS G130/G150
394 List Manual (LH2), 04/2014, A5E03263479A
Note: The value is automatically pre-assigned dependent on the motor when the drive system is first commissioned.
When calculating controller parameters (p0340 = 4), this value is re-calculated.
Description: Display and connector output for the output of the field weakening controller (synchronous motor) or the output of the
flux controller (separately-excited synchronous motor, induction motor).
Index: [0] = PI output
[1] = I output
Description: Sets the P gain of the field-weakening controller.
Description: Sets an additional setpoint for the field weakening controller.
The value refers to the dynamic voltage reserve (p1574).
Note: With a value equal to zero, when the target voltage limited with p1575 is reached, the field weakening controller is
activated.
Higher values mean that the field weakening controller intervenes later.
Description: Sets the integral-action time of the field-weakening controller.
r1593[0...1] CO: Field weakening controller / flux controller output / Field/Fl_ctrl outp
VECTOR_G (n/M) Can be changed: - Calculated: - Access level: 4
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 6723, 6724,
6726
P-Group: Closed-loop control Units group: 6_2 Unit selection: p0505
Not for motor type: REL Scaling: p2002 Expert list: 1
Min Max Factory setting
- [Arms] - [Arms] - [Arms]
p1594[0...n] Field-weakening controller P gain / Field_ctrl Kp
VECTOR_G (n/M) Can be changed: U, T Calculated: - Access level: 4
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 6724
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: ASM, REL, FEM Scaling: - Expert list: 1
Min Max Factory setting
0.00 1000.00 0.00
p1595[0...n] Field weakening controller additional setpoint / Field_ctr add_setp
VECTOR_G (n/M) Can be changed: U, T Calculated: - Access level: 4
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 6726
P-Group: - Units group: - Unit selection: -
Not for motor type: ASM, PEM, REL Scaling: - Expert list: 1
Min Max Factory setting
0.00 [%] 50.00 [%] 0.00 [%]
p1596[0...n] Field weakening controller integral-action time / Field_ctrl Tn
VECTOR_G (n/M) Can be changed: U, T Calculated: CALC_MOD_CON Access level: 3
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 6723, 6724
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: REL Scaling: - Expert list: 1
Min Max Factory setting
10 [ms] 10000 [ms] 50 [ms]