2 Parameters
2.2 List of parameters
Description: Sets the torque constant of the synchronous motor.
p0316 = 0:
The torque constant is calculated from the motor data.
p0316 > 0:
The selected value is used as torque constant.
Dependency: Refer to: r0334
Notice: When selecting a catalog motor (p0301), this parameter is automatically pre-assigned and is write protected.
Information in p0300 should be carefully observed when removing write protection.
Note: This parameter is not used for induction motors (p0300 = 1xx).
Description: Sets the stall current for synchronous motors (p0300 = 2xx).
Notice: When selecting a catalog motor (p0301), this parameter is automatically pre-assigned and is write protected.
Information in p0300 should be carefully observed when removing write protection.
Note: The parameter is used for the I2t monitoring of the motor (refer to p0611).
This parameter is not used for induction motors (p0300 = 1xx).
Description: Induction motors:
Sets the rated motor magnetizing current.
For p0320 = 0.000 the magnetizing current is internally calculated and displayed in r0331.
Synchronous motors:
Sets the rated motor short-circuit current.
Notice: When selecting a catalog motor (p0301), this parameter is automatically pre-assigned and is write protected.
Information in p0300 should be carefully observed when removing write protection.
Note: The magnetization current p0320 for induction motors (not for catalog motors) is reset when quick commissioning is
exited with p3900 > 0.
VECTOR:
If, for induction motors, the magnetizing current p0320 is changed outside the commissioning phase (p0010 > 0),
then the magnetizing inductance p0360 is changed so that the EMF r0337 remains constant.
p0316[0...n] Motor torque constant / Mot kT
VECTOR_G Can be changed: C2(1, 3), U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: MDS, p0130 Func. diagram: -
P-Group: Motor Units group: 28_1 Unit selection: p0100
Not for motor type: ASM, REL, FEM Scaling: - Expert list: 1
Min Max Factory setting
0.00 [Nm/A] 400.00 [Nm/A] 0.00 [Nm/A]
p0318[0...n] Motor stall current / Mot I_standstill
VECTOR_G Can be changed: C2(3) Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: MDS, p0130 Func. diagram: 8017
P-Group: Motor Units group: - Unit selection: -
Not for motor type: ASM, REL, FEM Scaling: - Expert list: 1
Min Max Factory setting
0.00 [Arms] 10000.00 [Arms] 0.00 [Arms]
p0320[0...n] Motor rated magnetizing current/short-circuit current / Mot I_mag_rated
VECTOR_G Can be changed: C2(3), U, T Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: MDS, p0130 Func. diagram: 5722
P-Group: Motor Units group: - Unit selection: -
Not for motor type: REL, FEM Scaling: - Expert list: 1
Min Max Factory setting
0.000 [Arms] 5000.000 [Arms] 0.000 [Arms]