SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
863
2 Parameters
2.2 List of parameters
Description: Sets the checksum for the checked Safety Integrated parameters of the motion monitoring function (reference
checksum) on the Motor Module/Hydraulic Module.
Index: [0] = Checksum over SI parameters for motion monitoring
[1] = Checksum over SI parameters with hardware reference
Dependency: Refer to: r9398
Note: SI: Safety Integrated
Description: Displays the parameters that were not able to be transferred when reading the parameter back-up files (PS files)
from the non-volatile memory (e.g. memory card).
r9406[0] = 0
--> All of the parameter values were able to be transferred error-free.
r9406[0...x] > 0
--> indicates the parameter number in the following cases:
- parameter, whose value was not able to be completely accepted.
- indexed parameter, where at least 1 index was not able to be accepted. The first index that is not transferred is
displayed in r9407.
Dependency: Refer to: r9407, r9408
Note: All indices from r9406 to r9408 designate the same parameter.
r9406[x] parameter number, parameter not accepted
r9407[x] parameter index, parameter not accepted
r9408[x] fault code, parameter not accepted
Description: Displays the first index of the parameters that could not be transferred when the parameter backup files (PS files)
were read from the non-volatile memory (e.g. memory card).
If, from an indexed parameter, at least one index was not able to be transferred, then the parameter number is
displayed in r9406[n] and the first index that was not transferred is displayed in r9407[n].
r9406[0] = 0
--> All of the parameter values were able to be transferred error-free.
r9406[n] > 0
--> Displays r9407[n] the first index of the parameter number r9406[n] that was not transferred.
Dependency: Refer to: r9406, r9408
p9399[0...1] SI Motion reference checksum SI parameters (Motor Module) / SI Mtn setp CRC MM
VECTOR_G Can be changed: C2(95) Calculated: - Access level: 3
Data type: Unsigned32 Dyn. index: - Func. diagram: -
P-Group: Safety Integrated Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0000 hex FFFF FFFF hex 0000 hex
r9406[0...19] PS file parameter number parameter not transferred / PS par_no n transf
All objects Can be changed: - Calculated: - Access level: 1
Data type: Unsigned16 Dyn. index: - Func. diagram: -
P-Group: - Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
r9407[0...19] PS file parameter index parameter not transferred / PS parameter index
All objects Can be changed: - Calculated: - Access level: 1
Data type: Unsigned16 Dyn. index: - Func. diagram: -
P-Group: - Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -