2 Parameters
2.2 List of parameters
Note: If value = 0:
No terminal assigned, selection bit remains statically at "0".
If value = 255:
No terminal assigned, selection bit remains statically at "1".
F-DI: Failsafe Digital Input
SLP: Safely-Limited Position
Description: Sets the input terminal for "special operating mode" (operating mode "function interface").
Value: 0: Statically active
1: F-DI 0 (X521.2/3/6)
2: F-DI 1 (X521.4/5/7)
3: F-DI 2 (X522.1/2/7)
4: F-DI 3 (X522.3/4/8)
5: F-DI 4 (X522.5/6/9)
6: F-DI 5 (X531.2/3/6)
7: F-DI 6 (X531.4/5/7)
8: F-DI 7 (X532.1/2/7)
9: F-DI 8 (X532.3/4/8)
10: F-DI 9 (X532.5/6/9)
255: Statically inact
Index: [0] = Drive group 1
[1] = Drive group 2
[2] = Drive group 3
[3] = Drive group 4
Note: Parameter being prepared. For this firmware version, the function interface is not supported.
If value = 0:
No terminal assigned, static special operation.
If value = 255:
No terminal assigned, static normal operation.
Description: Sets the input terminal for "agreement" (operating mode "function interface").
Value: 0: Statically active
1: F-DI 0 (X521.2/3/6)
2: F-DI 1 (X521.4/5/7)
3: F-DI 2 (X522.1/2/7)
4: F-DI 3 (X522.3/4/8)
5: F-DI 4 (X522.5/6/9)
6: F-DI 5 (X531.2/3/6)
7: F-DI 6 (X531.4/5/7)
8: F-DI 7 (X532.1/2/7)
9: F-DI 8 (X532.3/4/8)
10: F-DI 9 (X532.5/6/9)
255: Statically inact
p10036[0...3] SI TM54F special operating mode input terminal / SI spec mode F-DI
TM54F_MA,
TM54F_SL
Can be changed: C2(95) Calculated: - Access level: 4
Data type: Integer16 Dyn. index: - Func. diagram: -
P-Group: Safety Integrated Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 255 0
p10037[0...3] SI TM54F agreement input terminal / SI agreement F-DI
TM54F_MA,
TM54F_SL
Can be changed: C2(95) Calculated: - Access level: 4
Data type: Integer16 Dyn. index: - Func. diagram: -
P-Group: Safety Integrated Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 255 0