SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
291
2 Parameters
2.2 List of parameters
Re bit 03:
0: Non-volatile data save de-activated.
1: The setpoint for the motorized potentiometer is saved in a non-volatile fashion (for bit 00 = 1).
Re bit 04:
When the bit is set, the ramp-function generator is computed independent of the pulse enable. The actual output
value of the motorized potentiometer is always in r1050.
Description: Sets the signal source to continually increase the setpoint for the motorized potentiometer.
The setpoint change (CO: r1050) depends on the set ramp-up time (p1047) and the duration of the signal that is
present (BI: p1035).
Dependency: Refer to: p1036
Notice: The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Description: Sets the signal source to continuously lower the setpoint for the motorized potentiometer.
The setpoint change (CO: r1050) depends on the set ramp-down time (p1048) and the duration of the signal that is
present (BI: p1036).
Dependency: Refer to: p1035
Notice: The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Description: Sets the maximum speed/velocity for the motorized potentiometer.
Note: This parameter is automatically pre-assigned in the commissioning phase.
The setpoint output from the motorized potentiometer is limited to this value.
Description: Sets the minimum speed/velocity for the motorized potentiometer.
p1035[0...n] BI: Motorized potentiometer setpoint raise / Mop raise
VECTOR_G Can be changed: T Calculated: - Access level: 3
Data type: Unsigned32 / Binary Dyn. index: CDS, p0170 Func. diagram: 2505, 3020
P-Group: Setpoints Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0
p1036[0...n] BI: Motorized potentiometer lower setpoint / Mop lower
VECTOR_G Can be changed: T Calculated: - Access level: 3
Data type: Unsigned32 / Binary Dyn. index: CDS, p0170 Func. diagram: 2505, 3020
P-Group: Setpoints Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0
p1037[0...n] Motorized potentiometer maximum speed / MotP n_max
VECTOR_G Can be changed: U, T Calculated:
CALC_MOD_LIM_REF
Access level: 2
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 3020
P-Group: Setpoints Units group: 3_1 Unit selection: p0505
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
-210000.000 [rpm] 210000.000 [rpm] 0.000 [rpm]
p1038[0...n] Motorized potentiometer minimum speed / MotP n_min
VECTOR_G Can be changed: U, T Calculated:
CALC_MOD_LIM_REF
Access level: 2
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 3020
P-Group: Setpoints Units group: 3_1 Unit selection: p0505
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
-210000.000 [rpm] 210000.000 [rpm] 0.000 [rpm]