2 Parameters
2.2 List of parameters
SINAMICS G130/G150
724 List Manual (LH2), 04/2014, A5E03263479A
When acknowledging a replacement, the "Generate report" function is automatically executed.
p7786.x is automatically set to 0 after POWER ON.
Notice: This write process can take several minutes.
Note: The power unit involved can be assigned the correct P index using p0124 (power unit detection via LED).
Description: Setting of the tolerance window for the sign of life monitoring for communication to the power unit.
Note: An active window is generated by means of DRIVE-CLiQ telegrams.
If more than one sign-of-life error appears in the window, then A30853 is output.
The lower the value in p7788, the greater the monitoring tolerance.
Description: Sets the number of consecutive sign-of-life errors that are tolerated for communication to the power unit.
Note: F30008 is output in the case of a fault.
The higher the value in the parameter, the higher the monitoring tolerance.
Description: Sets the individual signals for the component trace.
Bit field: Bit Signal name 1 signal 0 signal FP
00 Control Interface Module (CIM) replaced Yes No -
01 Valve 1 replaced Yes No -
02 Valve 2 replaced Yes No -
03 Valve 3 replaced Yes No -
04 Valve 4 replaced Yes No -
05 Valve 5 replaced Yes No -
06 Valve 6 replaced Yes No -
15 Generate log Yes No -
p7788 Power unit sign-of-life monitoring tolerance window / PU SoL monit tol
B_INF, VECTOR_G Can be changed: U, T Calculated: - Access level: 4
Data type: Unsigned16 Dyn. index: - Func. diagram: -
P-Group: Converter Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
1 1000 10
p7789 Power unit sign-of-life monitoring fault threshold / PU SoL monit F_thr
B_INF, VECTOR_G Can be changed: U, T Calculated: - Access level: 4
Data type: Unsigned16 Dyn. index: - Func. diagram: -
P-Group: Converter Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 1000 1
p7790[0...15] Component trace signal / Comp trace sig
B_INF, VECTOR_G Can be changed: U, T Calculated: - Access level: 4
Data type: Integer16 Dyn. index: - Func. diagram: -
P-Group: Converter Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 9 [0] 2
[1] 3
[2] 4
[3] 7
[4] 8
[5] 9
[6] 5
[7] 0
[8] 6
[9] 1
[10...15] 0