SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
231
2 Parameters
2.2 List of parameters
Note: For p0651 = 0, the operating hours counter is disabled.
When setting p0651 to 0, then p0650 is automatically set to 0.
The operating hours counter only runs with motor data set 0 and 1 (MDS).
Description: Sets the factor to evaluate the stator resistance.
Dependency: Refer to: p0350, r0370
Description: Sets the factor to evaluate the stator leakage induction.
Dependency: Refer to: p0356, r0377
Description: Factor to evaluate the magnetizing inductance in the direction of the rotor axis (d axis).
Dependency: Refer to: p0360, r0382
Description: Factor to evaluate the magnetizing inductance quadrature to the rotor axis (q axis).
Dependency: Refer to: p0361, r0383
Description: Factor to evaluate the damping inductance in the direction of the rotor axis (d axis).
p0652[0...n] Motor stator resistance scaling / Mot R_stator scal
VECTOR_G Can be changed: C2(3), U, T Calculated: CALC_MOD_EQU Access level: 4
Data type: FloatingPoint32 Dyn. index: MDS, p0130 Func. diagram: -
P-Group: Motor Units group: - Unit selection: -
Not for motor type: ASM, PEM, REL Scaling: - Expert list: 1
Min Max Factory setting
10.0 [%] 300.0 [%] 100.0 [%]
p0653[0...n] Motor stator leakage inductance scaling / Mot L_S_leak scal
VECTOR_G Can be changed: C2(3), U, T Calculated: CALC_MOD_EQU Access level: 4
Data type: FloatingPoint32 Dyn. index: MDS, p0130 Func. diagram: -
P-Group: Motor Units group: - Unit selection: -
Not for motor type: ASM, PEM, REL Scaling: - Expert list: 1
Min Max Factory setting
10.0 [%] 300.0 [%] 100.0 [%]
p0655[0...n] Motor magnetizing inductance d axis saturated scaling / Mot L_m d sat scal
VECTOR_G Can be changed: C2(3), U, T Calculated: CALC_MOD_EQU Access level: 4
Data type: FloatingPoint32 Dyn. index: MDS, p0130 Func. diagram: 6727
P-Group: Motor Units group: - Unit selection: -
Not for motor type: ASM, PEM, REL Scaling: - Expert list: 1
Min Max Factory setting
10.0 [%] 300.0 [%] 100.0 [%]
p0656[0...n] Motor magnetizing inductance q axis saturated scaling / Mot L_m q sat scal
VECTOR_G Can be changed: C2(3), U, T Calculated: CALC_MOD_EQU Access level: 4
Data type: FloatingPoint32 Dyn. index: MDS, p0130 Func. diagram: 6727
P-Group: Motor Units group: - Unit selection: -
Not for motor type: ASM, PEM, REL Scaling: - Expert list: 1
Min Max Factory setting
10.0 [%] 300.0 [%] 100.0 [%]
p0657[0...n] Motor damping inductance d axis scaling / Mot L_damp d scal
VECTOR_G Can be changed: C2(3), U, T Calculated: CALC_MOD_EQU Access level: 4
Data type: FloatingPoint32 Dyn. index: MDS, p0130 Func. diagram: 6727
P-Group: Motor Units group: - Unit selection: -
Not for motor type: ASM, PEM, REL Scaling: - Expert list: 1
Min Max Factory setting
10.0 [%] 300.0 [%] 100.0 [%]