2 Parameters
2.2 List of parameters
SINAMICS G130/G150
890 List Manual (LH2), 04/2014, A5E03263479A
Description: Sets the velocity hysteresis for the SSM feedback signal to detect standstill (n < nx).
Note: The velocity hysteresis is effective only if the function is enabled (p9501.16 = 1).
The parameter is included in the crosswise data comparison of the two monitoring channels.
SSM: Safe Speed Monitor (safety-relevant feedback signal from the velocity monitoring)
Description: Sets the velocity hysteresis for the SSM feedback signal to detect standstill (n < nx).
Note: The velocity hysteresis is effective only if the function is enabled (p9501.16 = 1).
The parameter is included in the crosswise data comparison of the two monitoring channels.
SSM: Safe Speed Monitor (safety-relevant feedback signal from the velocity monitoring)
Description: Sets the velocity tolerance for the "SAM" function.
Note: SAM: Safe Acceleration Monitor (safe acceleration monitoring)
Description: Sets the velocity tolerance for the "SAM" function.
Note: SAM: Safe Acceleration Monitor (safe acceleration monitoring)
p9547 SI Motion SSM (SGA n < nx) velocity hysteresis (CU) / SI Mtn SSM hyst CU
VECTOR_G Can be changed: C2(95) Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 2823
P-Group: Safety Integrated Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.0010 [mm/min] 500.0000 [mm/min] 10.0000 [mm/min]
p9547 SI Motion SSM (SGA n < nx) velocity hysteresis (CU) / SI Mtn SSM hyst CU
VECTOR_G (Safety
rot)
Can be changed: C2(95) Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 2823
P-Group: Safety Integrated Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.0010 [rpm] 500.0000 [rpm] 10.0000 [rpm]
p9548 SI Motion SAM actual velocity tolerance (Control Unit) / SI Mtn SAM tol CU
VECTOR_G Can be changed: C2(95) Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: -
P-Group: Safety Integrated Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.00 [mm/min] 120000.00 [mm/min] 300.00 [mm/min]
p9548 SI Motion SAM actual velocity tolerance (Control Unit) / SI Mtn SAM tol CU
VECTOR_G (Safety
rot)
Can be changed: C2(95) Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: -
P-Group: Safety Integrated Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.00 [rpm] 120000.00 [rpm] 300.00 [rpm]