SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
141
2 Parameters
2.2 List of parameters
Dependency: The following applies for the magnetizing currents:
p0366 < p0367 < p0368 < p0369
The following applies for the stator quadrature axis current values (PESM):
20 % < p0366 < p0367 < p0368 < p0369
Refer to: p0362
Notice: For permanent-magnet synchronous motors (PESM), the following applies:
If the parameters are not set as specified, i.e. not in ascending order and to more than 20 %, the unsaturated
quadrature inductance (p0356) is always used for quadrature axis flux calculation purposes.
Note: When quick commissioning is exited with p3900 > 0, then the parameter is reset if a catalog motor has not been
selected (p0300).
Description: The saturation characteristic (flux as mapping of current) is defined using 4 points.
This parameter specifies the x coordinate for the 2nd value pair of the characteristic.
Induction motors (ASM) and separately-excited synchronous motors (SESM):
The saturation characteristic describes the mapping of the magnetizing current onto the motor flux.
The parameter sets the second magnetizing current as a [%] referred to the rated magnetizing current r0331 (ASM),
which in turn is referred to the no-load excitation current (SESM).
Permanent-magnet synchronous motors (PESM):
The saturation characteristic describes the mapping of the stator quadrature axis current onto the stator quadrature
axis flux.
The parameter sets the second stator quadrature axis current as a [%] referred to the rated motor current (p0305).
Dependency: The following applies for the magnetizing currents:
p0366 < p0367 < p0368 < p0369
The following applies for the stator quadrature axis current values (PESM):
20 % < p0366 < p0367 < p0368 < p0369
Refer to: p0363
Notice: For permanent-magnet synchronous motors (PESM), the following applies:
If the parameters are not set as specified, i.e. not in ascending order and to more than 20 %, the unsaturated
quadrature inductance (p0356) is always used for quadrature axis flux calculation purposes.
Note: When quick commissioning is exited with p3900 > 0, then the parameter is reset if a catalog motor has not been
selected (p0300).
Description: The saturation characteristic (flux as mapping of current) is defined using 4 points.
This parameter specifies the x coordinate for the 3rd value pair of the characteristic.
Induction motors (ASM) and separately-excited synchronous motors (SESM):
The saturation characteristic describes the mapping of the magnetizing current onto the motor flux.
The parameter sets the third magnetizing current as a [%] referred to the rated magnetizing current r0331 (ASM),
which in turn is referred to the no-load excitation current (SESM).
p0367[0...n] Motor saturation characteristic I_mag 2 / Mot sat. I_mag 2
VECTOR_G Can be changed: C2(3), U, T Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: MDS, p0130 Func. diagram: 6723, 6726
P-Group: Motor Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
5.0 [%] 800.0 [%] 75.0 [%]
p0368[0...n] Motor saturation characteristic I_mag 3 / Mot sat. I_mag 3
VECTOR_G Can be changed: C2(3), U, T Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: MDS, p0130 Func. diagram: 6723, 6726
P-Group: Motor Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
5.0 [%] 800.0 [%] 150.0 [%]