List Manual (LH2), 04/2014, A5E03263479A
533
2 Parameters
2.2 List of parameters
Description: Displays the setpoint memory for the motorized potentiometer of the technology controller.
For p2230.0 = 1, the last setpoint that was saved is entered after ON.
Dependency: Refer to: p2230
Description: Sets the signal source to continually increase the setpoint for the motorized potentiometer of the technology
controller.
The setpoint change (CO: r2250) depends on the set ramp-up time (p2247) and the duration of the signal that is
present (BI: p2235).
Dependency: Refer to: p2236
Description: Sets the signal source to continually reduce the setpoint for the motorized potentiometer of the technology controller.
The setpoint change (CO: r2250) depends on the set ramp-down time (p2248) and the duration of the signal that is
present (BI: p2236).
Dependency: Refer to: p2235
Description: Sets the maximum value for the motorized potentiometer of the technology controller.
Dependency: Refer to: p2238
r2231 Technology controller motorized potentiometer setpoint memory / Tec_ctrl mop mem
VECTOR_G
(Tech_ctrl)
Can be changed: - Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 7954
P-Group: Technology Units group: 9_1 Unit selection: p0595
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- [%] - [%] - [%]
p2235[0...n] BI: Technology controller motorized potentiometer raise setpoint / Tec_ctrl mop raise
VECTOR_G
(Tech_ctrl)
Can be changed: T Calculated: - Access level: 3
Data type: Unsigned32 / Binary Dyn. index: CDS, p0170 Func. diagram: 7954
P-Group: Commands Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0
p2236[0...n] BI: Technology controller motorized potentiometer lower setpoint /
Tec_ctrl mop lower
VECTOR_G
(Tech_ctrl)
Can be changed: T Calculated: - Access level: 3
Data type: Unsigned32 / Binary Dyn. index: CDS, p0170 Func. diagram: 7954
P-Group: Commands Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0
p2237[0...n] Technology controller motorized potentiometer maximum value / Tec_ctrl mop max
VECTOR_G
(Tech_ctrl)
Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 7954
P-Group: Technology Units group: 9_1 Unit selection: p0595
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
-200.00 [%] 200.00 [%] 100.00 [%]