SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
307
2 Parameters
2.2 List of parameters
BI: p1141 = 1 signal:
Continue ramp-function generator.
Dependency: Refer to: p1140, p1142
Caution: When "master control from PC" is activated, this binector input is ineffective.
Notice: The ramp-function generator is, independent of the state of the signal source, active in the following cases:
- OFF1/OFF3.
- ramp-function generator output within the suppression bandwidth.
- ramp-function generator output below the minimum speed.
Description: Sets the signal source for the command "enable setpoint/inhibit setpoint".
For the PROFIdrive profile, this command corresponds to control word 1 bit 6 (STW1.6).
BI: p1142 = 0 signal
Inhibits the setpoint (the ramp-function generator input is set to zero).
BI: p1142 = 1 signal
Setpoint enable.
Dependency: Refer to: p1140, p1141
Caution: When "master control from PC" is activated, this binector input is ineffective.
Notice: The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note: When the function module "position control" (r0108.3 = 1) is activated, this binector input is interconnected as follows
as standard:
BI: p1142 = 0 signal
Description: Sets the signal source for accepting the setting value of the ramp-function generator.
Dependency: The signal source for the ramp-function generator setting value is set using parameters.
Refer to: p1144
Note: 0/1 signal:
The ramp-function generator output is immediately (without delay) set to the setting value of the ramp-function
generator.
1 signal:
The setting value of the ramp-function generator is effective.
1/0 signal:
The input value of the ramp-function generator is effective. The ramp-function generator output is adapted to the
input value using the ramp-up time or the ramp-down time.
0 signal:
The input value of the ramp-function generator is effective.
p1142[0...n] BI: Enable setpoint/inhibit setpoint / Setpoint enable
VECTOR_G Can be changed: T Calculated: - Access level: 3
Data type: Unsigned32 / Binary Dyn. index: CDS, p0170 Func. diagram: 2501
P-Group: Setpoints Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 1
p1143[0...n] BI: Ramp-function generator, accept setting value / RFG accept set v
VECTOR_G Can be changed: T Calculated: - Access level: 3
Data type: Unsigned32 / Binary Dyn. index: CDS, p0170 Func. diagram: 3060, 3070
P-Group: Setpoints Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0