SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
409
2 Parameters
2.2 List of parameters
Dependency: Current setpoint filter 2 is activated via p1656.1 and parameterized via p1662 ... p1666.
Note: For a general 2nd-order filter, by inserting the same natural frequency in both the numerator and in the denominator,
i.e. bandstop frequency, a bandstop filter is implemented. If the numerator damping of zero is selected, the bandstop
frequency is completely suppressed.
The denominator damping can be determined from the equation for the 3 dB bandwidth:
f_3dB bandwidth = 2 * D_denominator * f_bandstop frequency
Description: Sets the denominator natural frequency for current setpoint filter 2 (PT2, general filter).
Dependency: Current setpoint filter 2 is activated via p1656.1 and parameterized via p1662 ... p1666.
Description: Sets the denominator damping for current setpoint filter 2.
Dependency: Current setpoint filter 2 is activated via p1656.1 and parameterized via p1662 ... p1666.
Description: Sets the numerator natural frequency for current setpoint filter 2 (general filter).
Dependency: Current setpoint filter 2 is activated via p1656.1 and parameterized via p1662 ... p1666.
Description: Sets the numerator damping for current setpoint filter 2.
Dependency: Current setpoint filter 2 is activated via p1656.1 and parameterized via p1662 ... p1666.
p1663[0...n] Current setpoint filter 2 denominator natural frequency / I_set_filt 2 fn_d
VECTOR_G (n/M) Can be changed: U, T Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 5710, 6710
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: REL Scaling: - Expert list: 1
Min Max Factory setting
0.5 [Hz] 16000.0 [Hz] 1999.0 [Hz]
p1664[0...n] Current setpoint filter 2 denominator damping / I_set_filt 2 D_d
VECTOR_G (n/M) Can be changed: U, T Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 5710, 6710
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: REL Scaling: - Expert list: 1
Min Max Factory setting
0.001 10.000 0.700
p1665[0...n] Current setpoint filter 2 numerator natural frequency / I_set_filt 2 fn_n
VECTOR_G (n/M) Can be changed: U, T Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 5710, 6710
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: REL Scaling: - Expert list: 1
Min Max Factory setting
0.5 [Hz] 16000.0 [Hz] 1999.0 [Hz]
p1666[0...n] Current setpoint filter 2 numerator damping / I_set_filt 2 D_n
VECTOR_G (n/M) Can be changed: U, T Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 5710, 6710
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: REL Scaling: - Expert list: 1
Min Max Factory setting
0.000 10.000 0.700