2 Parameters
2.2 List of parameters
Description: Sets the scaled proportional gain for the DC link voltage controller (Vdc controller).
Note: A value of 100% corresponds to the basic setting derived from the loop control parameter (p3422).
Description: Sets the scaled integral time for the DC link voltage controller (Vdc).
Note: A value of 100% corresponds to the basic setting derived from the loop control parameter (p3422).
Description: Sets the voltage scaler for the Voltage Sensing Module (VSM).
Note: When the 690 V input is used (X522) without voltage scaler, 0 % should be entered.
When the 100 V input (X521) is used with voltage scaler to measure medium voltages, the dividing (scaling) factor
multiplied by 100% should be entered.
Example:
1000 V line supply voltage, voltage scaling, 10:1
--> voltage at the VSM input is 100 V
--> p3660 = 10 * 100 % = 1000 %
Description: Displays the input voltage between phases L1 and L2 for the Voltage Sensing Module (VSM).
Dependency: Refer to: p3660
Note: X521.1 or X522.1: Connection of L1
X521.2 or X522.2: Connection of L2
X521.3 or X522.3: Connection of L3
p3560 Vdc controller proportional gain / Vdc_ctrl Kp
VECTOR_G
(Tech_ctrl)
Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 7960
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.01 [%] 1000.00 [%] 100.00 [%]
p3562 Vdc controller integral time / Vdc_ctrl Tn
VECTOR_G
(Tech_ctrl)
Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 7960
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.10 [%] 100000.00 [%] 100.00 [%]
p3660[0...n] VSM input line supply voltage voltage scaler / VSM inp U_scaler
VECTOR_G Can be changed: T Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: p0150 Func. diagram: 9880
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: - Scaling: PERCENT Expert list: 1
Min Max Factory setting
0.00 [%] 100000.00 [%] 0.00 [%]
r3661[0...n] CO: VSM input line supply voltage u1 - u2 / VSM inp u1-u2
VECTOR_G Can be changed: - Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: p0150 Func. diagram: -
P-Group: Closed-loop control Units group: 5_3 Unit selection: p0505
Not for motor type: - Scaling: p2001 Expert list: 1
Min Max Factory setting
- [V] - [V] - [V]