2 Parameters
2.2 List of parameters
SINAMICS G130/G150
526 List Manual (LH2), 04/2014, A5E03263479A
Description: Display and BICO output for the second status word of the monitoring functions.
Note: Re bit 10:
The torque threshold value 1 is set in p2174.
Re bit 12:
This bit is reset after the fault cause disappears, even if the fault itself is still present.
Description: Display and BICO output for the third status word of the monitoring functions.
Note: Re bit 00:
The speed threshold value 3 is set in p2161.
Re bit 01:
The comparison value is set in p2141. We recommend setting the hysteresis (p2142) for canceling the bit to a value
lower than that in p2141. Otherwise, the bit is not reset.
Re bit 11:
The torque threshold value 2 is set in p2194.
r2198.4...12 CO/BO: Status word monitoring 2 / ZSW monitor 2
VECTOR_G Can be changed: - Calculated: - Access level: 2
Data type: Unsigned16 Dyn. index: - Func. diagram: 2536
P-Group: Messages Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
04 |n_set| < p2161 Yes No 8011
05 n_set > 0 Yes No 8011
06 Motor blocked Yes No 8012
07 Motor stalled Yes No 8012
10 |M_set| < torque threshold value 1 Yes No 8012
11 Load monitoring signals an alarm Yes No 8013
12 Load monitoring signals a fault condition Yes No 8013
r2199.0...12 CO/BO: Status word monitoring 3 / ZSW monitor 3
VECTOR_G Can be changed: - Calculated: - Access level: 2
Data type: Unsigned16 Dyn. index: - Func. diagram: 2537
P-Group: Messages Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 |n_act| < speed threshold value 3 Yes No 8010
01 f or n comparison value reached or
exceeded
Yes No 8010
04 Speed setp - act val deviation in tolerance
t_on
Yes No 8011
05 Ramp-up/ramp-down completed Yes No 8011
06 Current below the zero current threshold Yes No 8018
07 Speed deviation model/external in tolerance Yes No 8012
11 Torque utilization < torque threshold value 2 Yes No 8012
12 Excitation current outside the tolerance
range
Yes No 8018