2 Parameters
2.2 List of parameters
SINAMICS G130/G150
612 List Manual (LH2), 04/2014, A5E03263479A
Index: [0] = AI 0 (X521.1/X521.2, S5.0)
[1] = AI 1 (X521.3/X521.4, S5.1)
Description: Sets the offset for the analog inputs of Terminal Board 30 (TB30).
The offset is added to the input signal before the scaling characteristic.
Index: [0] = AI 0 (X482.1/X482.2)
[1] = AI 1 (X482.3/X482.4)
Description: Sets the offset for the analog inputs of Terminal Module 31 (TM31).
The offset is added to the input signal before the scaling characteristic.
Index: [0] = AI 0 (X521.1/X521.2, S5.0)
[1] = AI 1 (X521.3/X521.4, S5.1)
Description: Activates the absolute value generation for the analog input signals of the Terminal Board 30 (TB30).
Value: 0: No absolute value generation
1: Absolute value generation switched in
Index: [0] = AI 0 (X482.1/X482.2)
[1] = AI 1 (X482.3/X482.4)
Description: Activates the absolute value generation for the analog input signals of Terminal Module 31 (TM31).
Value: 0: No absolute value generation
1: Absolute value generation switched in
Index: [0] = AI 0 (X521.1/X521.2, S5.0)
[1] = AI 1 (X521.3/X521.4, S5.1)
p4063[0...1] TB30 analog inputs offset / TB30 AI offset
TB30 Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 9104
P-Group: Terminals Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
-20.000 [V] 20.000 [V] 0.000 [V]
p4063[0...1] TM31 analog inputs offset / TM31 AI offset
TM31 Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 9566, 9568
P-Group: Terminals Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
-20.000 20.000 0.000
p4066[0...1] TB30 analog inputs activate absolute value generation / TB30 AI absVal act
TB30 Can be changed: U, T Calculated: - Access level: 3
Data type: Integer16 Dyn. index: - Func. diagram: 9104
P-Group: Terminals Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 1 0
p4066[0...1] TM31 analog inputs activate absolute value generation / TM31 AI absVal act
TM31 Can be changed: U, T Calculated: - Access level: 3
Data type: Integer16 Dyn. index: - Func. diagram: 9566, 9568
P-Group: Terminals Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 1 0