2 Parameters
2.2 List of parameters
SINAMICS G130/G150
382 List Manual (LH2), 04/2014, A5E03263479A
Description: Sets the signal source for the lower torque limit.
Dependency: Refer to: p1520, p1521, p1522
Danger: Positive values resulting from the signal source and scaling can cause the motor to accelerate in an uncontrolled
manner.
Description: Sets the scaling for the upper torque limit.
Notice: A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
Note: This parameter can be freely interconnected.
The value has the meaning stated above if it is interconnected from connector input p1528.
Description: Sets the scaling for the lower torque limit.
Notice: A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
Note: This parameter can be freely interconnected.
The value has the meaning stated above if it is interconnected from connector input p1528.
Description: Display and connector output for the upper torque limit of all torque limits without offset.
Dependency: Refer to: p1520, p1521, p1522, p1523, p1528, p1529
p1523[0...n] CI: Torque limit lower / M_max lower
VECTOR_G (n/M) Can be changed: T Calculated: - Access level: 3
Data type: Unsigned32 / FloatingPoint32 Dyn. index: CDS, p0170 Func. diagram: 6020, 6630
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: REL Scaling: p2003 Expert list: 1
Min Max Factory setting
- - 1521[0]
p1524[0...n] CO: Torque limit upper scaling / M_max upper scal
VECTOR_G (n/M) Can be changed: U, T Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 6630
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: REL Scaling: PERCENT Expert list: 1
Min Max Factory setting
-2000.0 [%] 2000.0 [%] 100.0 [%]
p1525[0...n] CO: Torque limit lower scaling / M_max lower scal
VECTOR_G (n/M) Can be changed: U, T Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 6630
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: REL Scaling: PERCENT Expert list: 1
Min Max Factory setting
-2000.0 [%] 2000.0 [%] 100.0 [%]
r1526 CO: Torque limit upper without offset / M_max up w/o offs
VECTOR_G (n/M) Can be changed: - Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 6060, 6630,
6640
P-Group: Closed-loop control Units group: 7_1 Unit selection: p0505
Not for motor type: REL Scaling: p2003 Expert list: 1
Min Max Factory setting
- [Nm] - [Nm] - [Nm]