2 Parameters
2.2 List of parameters
SINAMICS G130/G150
692 List Manual (LH2), 04/2014, A5E03263479A
Dependency: This parameter can only be changed if p5300=0 has been parameterized.
Refer to: p5300
Caution: Please note the general conditions of the moment of inertia estimator, online tuning and adaptive resonance filter.
See Function Manual FH1.
Note: Re bit 00: being prepared
The speed controller gain is determined and set using a noise signal.
Re bit 01: being prepared
Possibly required current setpoint filters are determined and set using a noise signal.
As a consequence, a higher dynamic performance can be achieved in the speed control loop.
Re bit 02:
Using this bit, the moment of inertia is determined while traversing (moment of inertia estimator). If this bit is not set,
then the load moment of inertia must be manually parameterized in parameter p1498.
Re bit 03:
If "once" has been parameterized, then after successfully determining the moment of inertia p1498 the moment of
inertia estimator is deactivated.
If "Cyclic" has been parameterized, then the moment of inertia is continually determined and the controller
parameters adapted. After the moment of inertia has been successfully determined (r1407.26=1), we recommend
that the parameter is saved. This means that after power on, the controller does not have to re-stabilize.
Re bit 06:
The adaptation of a current setpoint filter can be set here. See p5280-p5285.
This adaptation may be necessary if a mechanical resonance frequency changes in operation. It can also be used to
dampen a fixed resonance frequency. Once the control loop has stabilized, this bit should be deactivated and the
determined parameters saved in a non-volatile fashion.
Re bit 07:
With this function, these axes are adapted to the dynamic response set in p5275. This is necessary for interpolating
axes. The time in p5275 should be set according to the axis with the lowest dynamic response.
Description: Displays the ambient temperature for motor temperature model 3.
This value is used to calculate the utilization display (p0034).
The parameter value is an image of p0613.
Dependency: Refer to: r0034
Note: Users cannot see and change parameter p0613 (only Siemens internal).
Bit field: Bit Signal name 1 signal 0 signal FP
00 Setting Kp Yes No -
01 Setting current setpoint filter Yes No -
02 Moment of inertia estimator Yes No -
03 Moment of inertia estimator Cyclic Once -
06 Current setpoint filter adaptation Yes No -
07 Synchronized axes Yes No -
r5397 Mot_temp_mod 3 ambient temperature image p0613 / AmbTmp image p0613
VECTOR_G Can be changed: - Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 8017
P-Group: Displays, signals Units group: 21_1 Unit selection: p0505
Not for motor type: ASM, REL, FEM Scaling: - Expert list: 1
Min Max Factory setting
- [°C] - [°C] - [°C]