SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
787
2 Parameters
2.2 List of parameters
- CAN CBC10 always communicates via IF2.
For a value not equal to 99 (automatic) the following applies:
- both indices must be set to a number not equal to 99 (automatic).
A change only becomes effective after POWER ON, reset or download.
Description: Sets the monitoring time to monitor the process data received via COMM BOARD.
If, during this time, the Control Unit does not receive any process data from the COMM BOARD, then an appropriate
message is output.
Note: This monitoring function only monitors the connection between the Control Unit and COMM BOARD and not the data
traffic on the fieldbus.
Value = 0: Monitoring is de-activated.
Description: Sets the send configuration data for the COMM BOARD.
The setting is activated with p8842.
Dependency: Refer to: p8842
Note: The configuration data are specific to the inserted COMM BOARD.
For CBE20, the configuration data are not relevant.
Description: Activate a modified send configuration for COMM BOARD.
With p8842 = 1, the values in p8841 are transferred to the COMM BOARD and activated. After this, p8842 is
automatically set to zero.
Dependency: Refer to: p8841
p8840 COMM BOARD monitoring time / CB t_monit
CU_G130_DP (COMM
BOARD, PROFINET
CBE20),
CU_G130_PN (COMM
BOARD, PROFINET
CBE20),
CU_G150_DP (COMM
BOARD, PROFINET
CBE20),
CU_G150_PN (COMM
BOARD, PROFINET
CBE20)
Can be changed: U, T Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: -
P-Group: Communications Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 [ms] 65535000 [ms] 20 [ms]
p8841[0...239] COMM BOARD send configuration data / CB s config_dat
CU_G130_DP (COMM
BOARD, PROFINET
CBE20),
CU_G130_PN (COMM
BOARD, PROFINET
CBE20),
CU_G150_DP (COMM
BOARD, PROFINET
CBE20),
CU_G150_PN (COMM
BOARD, PROFINET
CBE20)
Can be changed: U, T Calculated: - Access level: 3
Data type: Unsigned16 Dyn. index: - Func. diagram: -
P-Group: Communications Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 65535 0
p8842 Activate COMM BOARD send configuration / CB s config act
CU_G130_DP (COMM
BOARD, PROFINET
CBE20),
CU_G130_PN (COMM
BOARD, PROFINET
CBE20),
CU_G150_DP (COMM
BOARD, PROFINET
CBE20),
CU_G150_PN (COMM
BOARD, PROFINET
CBE20)
Can be changed: U, T Calculated: - Access level: 3
Data type: Unsigned16 Dyn. index: - Func. diagram: -
P-Group: Communications Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 1 0