SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
641
2 Parameters
2.2 List of parameters
Description: Sets the component number (p0141) of the encoder whose functional reserve is to be displayed (r4651).
Dependency: Refer to: r4651
Description: Displays the functional reserve of the encoder selected via p4650.
0 ... 25 %:
The function limit has been reached. A service is recommended.
26 ... 100 %:
The encoder is working in the specified range.
Index: [0] = Function reserve 1
[1] = Function reserve 2
[2] = Function reserve 3
[3] = Function reserve 4
Dependency: Refer to: p4650
Note: Value = 999 means:
- the component specified in p4650 is not connected
- the encoder does not support the display of the functional reserve
Description: Sets the mode to reset the actual value in XIST_ERW (CO: r4653).
Value: 0: Inactive
1: Reset with zero mark
2: Reset with BICO
3: Reset with selected zero mark
Dependency: Refer to: r4653, r4654, p4655
Note: If value = 1:
The value in XIST1_ERW is reset when passing every zero mark.
If value = 2:
The value in XIST1_ERW is reset with a 0/1 edge via binector input p4655.
If value = 3:
The value in XIST1_ERW is reset after a 0/1 edge via binector input p4655 when passing the next zero mark.
p4650 Encoder functional reserve component number / Enc fct_res num
CU_G130_DP,
CU_G130_PN,
CU_G150_DP,
CU_G150_PN
Can be changed: U, T Calculated: - Access level: 3
Data type: Unsigned16 Dyn. index: - Func. diagram: -
P-Group: Displays, signals Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 399 0
r4651[0...3] Encoder functional reserve / Enc fct_reserve
CU_G130_DP,
CU_G130_PN,
CU_G150_DP,
CU_G150_PN
Can be changed: - Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: -
P-Group: Displays, signals Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- [%] - [%] - [%]
p4652 XIST1_ERW reset mode / XIST1_ERW res mode
ENC Can be changed: C1(3) Calculated: - Access level: 3
Data type: Integer16 Dyn. index: - Func. diagram: 4750
P-Group: - Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 3 0