2 Parameters
2.2 List of parameters
SINAMICS G130/G150
254 List Manual (LH2), 04/2014, A5E03263479A
Description: Sets the configuration for the motor and encoder changeover.
Note: Re bit 00:
When the bit is set and the motor has to be changed over, then p0827 must be set differently in the appropriate motor
data sets.
Re bit 02:
The bit defines whether, for an EDS changeover, the status signal Gn_ZSW.14 is suppressed (parking encoder
active).
Re motor changeover to running motor:
The "flying restart" function should also be activated (p1200) when changing over to a motor that is already running.
Description: Displays the status word for the drive data set changeover.
Note: Re bit 02:
A data set changeover is delayed by the time required for the internal parameter calculation.
Description: Displays the status word for the drive data set changeover.
p0833 Data set changeover configuration / DS_chng config
VECTOR_G Can be changed: C2(15) Calculated: - Access level: 2
Data type: Unsigned16 Dyn. index: - Func. diagram: 8575
P-Group: Data sets Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0010 bin
Bit field: Bit Signal name 1 signal 0 signal FP
00 Contactor changeover from the
application/drive
application Drive -
01 Pulse suppression by application/drive application Drive -
02 Suppress drive parking for EDS changeover Yes No -
r0835.2 CO/BO: Data set changeover status word / DDS_ZSW
ENC Can be changed: - Calculated: - Access level: 2
Data type: Unsigned16 Dyn. index: - Func. diagram: 8575
P-Group: Displays, signals Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
02 Internal parameter calculation active Yes No -
r0835.0...11 CO/BO: Data set changeover status word / DDS_ZSW
VECTOR_G Can be changed: - Calculated: - Access level: 2
Data type: Unsigned16 Dyn. index: - Func. diagram: 8575
P-Group: Displays, signals Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Motor changeover active Yes No 8575
01 Encoder changeover active Yes No -
02 Internal parameter calculation active Yes No -
04 Armature short circuit active Yes No -
05 Identification running Yes No -
06 Friction characteristic record running Yes No -
07 Rotating measurement running Yes No -
08 Motor data identification running Yes No -
10 Wait for pulse suppression Yes No -
11 Wait for motor changeover feedback signal Yes No -