EasyManua.ls Logo

Siemens SINAMICS G150 - Page 253

Siemens SINAMICS G150
1842 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
253
2 Parameters
2.2 List of parameters
Example:
A changeover is to be made between MDS0 (motor 0) and MDS1 (motor 1). The contactors should be switched using
bit 4 (contactor 0) and 5 (contactor 1). The changeover should be made with an interconnection of the feedback
signal.
Implementation:
MDS0: p0827[0] = 4, interconnect output to switch contactor 0 to r0830.4, p0831[4] = "input, feedback signal,
contactor 0"
MDS1: p0827[1] = 5, interconnect output to switch contactor 1 to r0830.5, p0831[5] = "input, feedback signal,
contactor 1"
The following sequence applies when changing over from MDS0 to MDS1:
1. The status bit r0830.4 is deleted. When the feedback signal (p0831[4]) is connected, the system waits until the
feedback signal "contactor open" is displayed. If the feedback signal is not connected, then the system waits for the
switch-off interlocking time of 320 ms.
2. The status bit r0830.5 is set. If the feedback signal (p0831[5]) is connected, the system waits until the feedback
signal "contactor closed" is displayed. If the feedback signal is not connected, then the system waits for the switch-on
interlocking time of 160 ms.
Index: [0] = Feedback signal contactor 0
[1] = Feedback signal contactor 1
[2] = Feedback signal contactor 2
[3] = Feedback signal contactor 3
[4] = Feedback signal contactor 4
[5] = Feedback signal contactor 5
[6] = Feedback signal contactor 6
[7] = Feedback signal contactor 7
[8] = Feedback signal contactor 8
[9] = Feedback signal contactor 9
[10] = Feedback signal contactor 10
[11] = Feedback signal contactor 11
[12] = Feedback signal contactor 12
[13] = Feedback signal contactor 13
[14] = Feedback signal contactor 14
[15] = Feedback signal contactor 15
Description: Displays the status word of the contactor feedback signals when changing over a motor.
Dependency: Refer to: p0831
r0832.0...15 CO/BO: Mot. changeover contactor feedback sig. status word / Mot_chng fdbk ZSW
VECTOR_G Can be changed: - Calculated: - Access level: 2
Data type: Unsigned32 Dyn. index: - Func. diagram: 8575
P-Group: Displays, signals Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Feedback signal contactor 0 Closed Opened -
01 Feedback signal contactor 1 Closed Opened -
02 Feedback signal contactor 2 Closed Opened -
03 Feedback signal contactor 3 Closed Opened -
04 Feedback signal contactor 4 Closed Opened -
05 Feedback signal contactor 5 Closed Opened -
06 Feedback signal contactor 6 Closed Opened -
07 Feedback signal contactor 7 Closed Opened -
08 Feedback signal contactor 8 Closed Opened -
09 Feedback signal contactor 9 Closed Opened -
10 Feedback signal contactor 10 Closed Opened -
11 Feedback signal contactor 11 Closed Opened -
12 Feedback signal contactor 12 Closed Opened -
13 Feedback signal contactor 13 Closed Opened -
14 Feedback signal contactor 14 Closed Opened -
15 Feedback signal contactor 15 Closed Opened -

Table of Contents

Other manuals for Siemens SINAMICS G150