2 Parameters
2.2 List of parameters
Description: Displays the value for the property set in p9206.
A value is only displayed for integer type properties.
Dependency: Refer to: p9206, r9208
Description: Displays the value for the property set in p9206.
A value is only displayed for string type properties.
Dependency: Refer to: p9206, r9207
Note: An ASCII table (excerpt) can be found, for example, in the appendix to the List Manual.
Description: Sets the component number for a component to get its status LED to flash.
Dependency: Refer to: p9211
Description: Sets the function for the component selected in p9210.
After initiating a function, the parameter is automatically reset again.
Example:
- Set the component number (p9210).
- Select the "flashing on" function (set p9211 = 1).
Value: -1: Select function
0: Flashing off
1: Flashing on
Dependency: Refer to: p9210
Notice: If a task cannot be executed (e.g. the component number in p9210 does not exist), the following applies:
- There is no negative feedback signal.
- The value is reset anyway.
r9207 Topology direct access integer value / Topo access int
CU_G130_DP,
CU_G130_PN,
CU_G150_DP,
CU_G150_PN
Can be changed: - Calculated: - Access level: 3
Data type: Unsigned32 Dyn. index: - Func. diagram: -
P-Group: Topology Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
r9208[0...50] Topology direct access string / Topo access string
CU_G130_DP,
CU_G130_PN,
CU_G150_DP,
CU_G150_PN
Can be changed: - Calculated: - Access level: 3
Data type: Unsigned8 Dyn. index: - Func. diagram: -
P-Group: Topology Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
p9210 Flashing component number / Flash comp_no
CU_G130_DP,
CU_G130_PN,
CU_G150_DP,
CU_G150_PN
Can be changed: U, T Calculated: - Access level: 3
Data type: Unsigned16 Dyn. index: - Func. diagram: -
P-Group: Topology Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 499 0
p9211 Flash function / Flash fct.
CU_G130_DP,
CU_G130_PN,
CU_G150_DP,
CU_G150_PN
Can be changed: U, T Calculated: - Access level: 3
Data type: Integer16 Dyn. index: - Func. diagram: -
P-Group: Topology Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
-1 1 -1