SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
805
2 Parameters
2.2 List of parameters
Note: Value range:
0: Not used
1 ... 16: Send telegram word
A specific telegram word send may only be used once within a single device.
A change only becomes effective after POWER ON, reset, project download or p8842 = 1.
Description: Selects the address of the SINAMICS Link sender from which the process data (PZD) is received.
Index: [0] = PZD 1
[1] = PZD 2
[2] = PZD 3
[3] = PZD 4
[4] = PZD 5
[5] = PZD 6
[6] = PZD 7
[7] = PZD 8
[8] = PZD 9
[9] = PZD 10
[10] = PZD 11
[11] = PZD 12
[12] = PZD 13
[13] = PZD 14
[14] = PZD 15
[15] = PZD 16
Dependency: Refer to: p8870
Note: Value range:
0: Not used
1 ... 64: Address
A change only becomes effective after POWER ON, reset, project download or p8842 = 1.
Description: Displays the bus address of sender from which the PZD is received.
Index: [0] = PZD 1
[1] = PZD 2
[2] = PZD 3
[3] = PZD 4
p8872[0...15] SINAMICS Link address receive PZD / Link addr recv
B_INF (PROFINET
CBE20),
CU_G130_DP
(PROFINET CBE20),
CU_G130_PN
(PROFINET CBE20),
CU_G150_DP
(PROFINET CBE20),
CU_G150_PN
(PROFINET CBE20),
ENC (PROFINET
CBE20), TB30
(PROFINET CBE20),
TM150 (PROFINET
CBE20), TM31
(PROFINET CBE20),
VECTOR_G
(PROFINET CBE20)
Can be changed: T Calculated: - Access level: 3
Data type: Unsigned16 Dyn. index: - Func. diagram: -
P-Group: Communications Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 64 0
r8874[0...9] IF2 diagnostics bus address PZD receive / IF2 diag addr recv
B_INF Can be changed: - Calculated: - Access level: 3
Data type: Unsigned16 Dyn. index: - Func. diagram: -
P-Group: Communications Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -