SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
655
2 Parameters
2.2 List of parameters
Description: Displays the motor order number (MLFB) of the data backup selected with p4693.
Dependency: Refer to: p4691, p4692
Caution: If the selected subdirectory contains a number of data sets, "More Datasets" is displayed in r4694[0...19].
If there is no SMI data (motor/encoder data) in the selected subdirectory or if the selected subdirectory does not exist,
the following applies:
- The number of the next subdirectory located is displayed.
- This subdirectory is not checked for valid SMI data.
- If another subdirectory cannot be located, nothing is displayed in r4694[0...19].
Note: SMI: SINAMICS Sensor Module Integrated
Description: Setting to control the trace function.
Value: 0: Stop trace
1: Start trace
Index: [0] = Trace 0
[1] = Trace 1
Description: Setting to control the measurement function.
Value: 0: Stop measuring function
1: Start measuring function
2: Measuring function check parameterization
3: Start measuring function without enable signals
Description: Sets the options for the trace.
Index: [0] = Trace 0
[1] = Trace 1
r4694[0...19] SMI spare part data backup motor order number / SMI dat_bkup MLFB
CU_G130_DP,
CU_G130_PN,
CU_G150_DP,
CU_G150_PN
Can be changed: - Calculated: - Access level: 3
Data type: Unsigned8 Dyn. index: - Func. diagram: -
P-Group: Displays, signals Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
p4700[0...1] Trace control / Trace control
CU_G130_DP,
CU_G130_PN,
CU_G150_DP,
CU_G150_PN
Can be changed: U, T Calculated: - Access level: 3
Data type: Integer16 Dyn. index: - Func. diagram: -
P-Group: Trace and function generator Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 0
Min Max Factory setting
0 1 0
p4701 Measuring function control / Meas fct ctrl
CU_G130_DP,
CU_G130_PN,
CU_G150_DP,
CU_G150_PN
Can be changed: U, T Calculated: - Access level: 3
Data type: Integer16 Dyn. index: - Func. diagram: -
P-Group: Trace and function generator Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 0
Min Max Factory setting
0 3 0
p4703[0...1] Trace options / Trace options
CU_G130_DP,
CU_G130_PN,
CU_G150_DP,
CU_G150_PN
Can be changed: T Calculated: - Access level: 3
Data type: Unsigned16 Dyn. index: - Func. diagram: -
P-Group: Trace and function generator Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 0
Min Max Factory setting
- - 0000 bin