2 Parameters
2.2 List of parameters
Description: The friction characteristic is defined by 10 value pairs.
This parameter specifies the n coordinate of the 9th value pair of the friction characteristic.
Dependency: Refer to: p3838, p3845
Description: The friction characteristic is defined by 10 value pairs.
This parameter specifies the n coordinate of the 10th value pair of the friction characteristic.
Dependency: Refer to: p3839, p3845
Description: The friction characteristic is defined by 10 value pairs.
This parameter specifies the M coordinate of the 1st value pair of the friction characteristic.
Dependency: Refer to: p3820, p3845
Description: The friction characteristic is defined by 10 value pairs.
This parameter specifies the M coordinate of the 2nd value pair of the friction characteristic.
Dependency: Refer to: p3821, p3845
p3828[0...n] Friction characteristic value n8 / Friction n8
VECTOR_G (n/M) Can be changed: T Calculated:
CALC_MOD_LIM_REF
Access level: 2
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 7010
P-Group: Functions Units group: 3_1 Unit selection: p0505
Not for motor type: REL Scaling: - Expert list: 1
Min Max Factory setting
0.00 [rpm] 210000.00 [rpm] 1500.00 [rpm]
p3829[0...n] Friction characteristic value n9 / Friction n9
VECTOR_G (n/M) Can be changed: T Calculated:
CALC_MOD_LIM_REF
Access level: 2
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 7010
P-Group: Functions Units group: 3_1 Unit selection: p0505
Not for motor type: REL Scaling: - Expert list: 1
Min Max Factory setting
0.00 [rpm] 210000.00 [rpm] 3000.00 [rpm]
p3830[0...n] Friction characteristic value M0 / Friction M0
VECTOR_G (n/M) Can be changed: T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 7010
P-Group: Functions Units group: 7_1 Unit selection: p0505
Not for motor type: REL Scaling: - Expert list: 1
Min Max Factory setting
-1000000.00 [Nm] 1000000.00 [Nm] 0.00 [Nm]
p3831[0...n] Friction characteristic value M1 / Friction M1
VECTOR_G (n/M) Can be changed: T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 7010
P-Group: Functions Units group: 7_1 Unit selection: p0505
Not for motor type: REL Scaling: - Expert list: 1
Min Max Factory setting
-1000000.00 [Nm] 1000000.00 [Nm] 0.00 [Nm]