2 Parameters
2.2 List of parameters
SINAMICS G130/G150
608 List Manual (LH2), 04/2014, A5E03263479A
Description: Displays the currently referred input value of the analog inputs of Terminal Module 31 (TM31).
When interconnected, the signals are referred to the reference quantities p200x and p205x.
Index: [0] = AI 0 (X521.1/X521.2, S5.0)
[1] = AI 1 (X521.3/X521.4, S5.1)
Note: AI: Analog Input
Description: Displays the type of analog inputs.
Value: 4: Bipolar voltage input (-10 V ... +10 V)
Index: [0] = AI 0 (X482.1/X482.2)
[1] = AI 1 (X482.3/X482.4)
Description: Sets the type of analog inputs of Terminal Module 31 (TM31).
p4056[x] = 0, 4 correspond to a voltage input (r4052, p4057, p4059 are displayed in V).
p4056[x] = 2, 3, 5 correspond to a current input (r4052, p4057, p4059 are displayed in mA).
In addition, the associated switch S5 must be appropriately set.
AI 0: S5.0 = V --> voltage input, S5.0 = I --> current input (burden resistor = 250 Ohm)
AI 1: S5.1 = V --> voltage input, S5.1 = I --> current input (burden resistor = 250 Ohm)
Value: 0: Unipolar voltage input (0 V ... +10 V)
2: Unipolar current input (0 mA ... +20 mA)
3: Unipolar current input monitored (+4 mA to +20 mA)
4: Bipolar voltage input (-10 V ... +10 V)
5: Bipolar current input (-20 mA to +20 mA)
Index: [0] = AI 0 (X521.1/X521.2, S5.0)
[1] = AI 1 (X521.3/X521.4, S5.1)
Warning: The maximum voltage difference between the analog input terminals AI+, AI- and the ground of the TM31 (X520.6,
X530.3) may not exceed 35 V.
For operation with the load resistor switched in, the voltage between the differential inputs AI+ and AI- may not
exceed 15 V or the impressed current of 60 mA; if this is not carefully observed, the input will be damaged.
Notice: For operation as a voltage input/current input, switch S5.0 or S5.1 must be appropriately set.
r4055[0...1] CO: TM31 analog inputs actual value in percent / TM31 AI value in %
TM31 Can be changed: - Calculated: - Access level: 1
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 9549, 9566,
9568
P-Group: Terminals Units group: - Unit selection: -
Not for motor type: - Scaling: PERCENT Expert list: 1
Min Max Factory setting
- [%] - [%] - [%]
r4056[0...1] TB30 analog inputs type / TB30 AI type
TB30 Can be changed: - Calculated: - Access level: 1
Data type: Integer16 Dyn. index: - Func. diagram: -
P-Group: Terminals Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
4 4 -
p4056[0...1] TM31 analog inputs type / TM31 AI type
TM31 Can be changed: U, T Calculated: - Access level: 1
Data type: Integer16 Dyn. index: - Func. diagram: 9566, 9568
P-Group: Terminals Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 5 4