2 Parameters
2.2 List of parameters
SINAMICS G130/G150
644 List Manual (LH2), 04/2014, A5E03263479A
Dependency: Refer to: p4652, r4653, r4654
Note: The reset of XIST1_ERW depends on the selected mode (p4652).
Description: Sets the filter bandwidth for Sensor Module SMx10 (resolver) and SMx20 (sin/cos).
The value set on the Sensor Module is displayed in r4661.
The Sensor Module hardware only supports the following values:
- 0: The Sensor Module's default is used.
- 50 kHz
- 170 kHz
- 500 kHz
- Unlimited: Only the bandwidth of the operational amplifier is effective.
Dependency: Refer to: r4661
Note: A value of zero is displayed if an encoder is not present.
Description: Sets the filter bandwidth for Sensor Module SMx10 (resolver) and SMx20 (sin/cos).
The value set on the Sensor Module is displayed in r4661.
The Sensor Module hardware only supports the following values:
- 0: The Sensor Module's default is used.
- 50 kHz
- 170 kHz
- 500 kHz
- Unlimited: Only the bandwidth of the operational amplifier is effective.
Index: [0] = Encoder 1
[1] = Encoder 2
[2] = Encoder 3
Dependency: Refer to: r4661
Note: A value of zero is displayed if an encoder is not present.
Description: Display of the effective filter bandwidth for Sensor Module SMx10 (resolver) and SMx20 (sin/cos).
The bandwidth of the filter is set using p4660.
Dependency: Refer to: p4660
Note: A value of zero is displayed if an encoder is not present.
p4660 Sensor Module filter bandwidth / SM Filt_bandw
ENC Can be changed: C2(4) Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: -
P-Group: Encoder Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.00 [kHz] 20000.00 [kHz] 0.00 [kHz]
p4660[0...2] Sensor Module filter bandwidth / SM Filt_bandw
VECTOR_G Can be changed: C2(4) Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: -
P-Group: Encoder Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.00 [kHz] 20000.00 [kHz] 0.00 [kHz]
r4661 Sensor Module filter bandwidth display / SM Filt_bandw disp
ENC Can be changed: - Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: -
P-Group: Encoder Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- [kHz] - [kHz] - [kHz]