2 Parameters
2.2 List of parameters
SINAMICS G130/G150
782 List Manual (LH2), 04/2014, A5E03263479A
Note: Re index 0:
Corresponds to the CANopen object 6071 hex + 800 hex * x (x: Drive number 0 ... 7).
The displayed parameter value is scaled via the reference torque p2003:
4000 hex corresponds to p2003
Description: The factor converts the required velocity units into the internal velocity units (U/s).
With the factory setting, for CANopen, the velocity units are increments/second.
The parameter corresponds to the CANopen object 6094 hex.
The internal velocity is calculated as follows:
n_set_internal = object 6094.1 / object 6094.2 * 1/(p0408 * 2^p0418) * n_set_bus
Index: [0] = Counter
[1] = Denominator
Description: Sets the configuration for the content of identification and maintenance 4 (I&M 4, p8809).
Value: 0: Standard value for I&M 4 (p8809)
1: User value for I&M 4 (p8809)
Dependency: For p8805 = 0, if the user writes at least one value in p8809[0...53], then p8805 is automatically set to = 1.
When p8805 is reset = 0, then the content of the factory setting is set in p8809.
Note: Re p8805 = 0:
PROFINET I&M 4 (p8809) contains the information for the SI change tracking.
Re p8805 = 1:
PROFINET I&M 4 (p8809) contains the values written by the user.
Description: Parameters for the PROFINET data set "Identification and Maintenance 1" (I&M 1).
This information is known as "System identifier" and "Location identifier".
Dependency: Refer to: p8807, p8808
Notice: Only characters belonging to the standard ASCII character set may be used (32 dec to 126 dec).
Note: An ASCII table (excerpt) can be found, for example, in the appendix to the List Manual.
Re p8806[0...31]:
System identifier.
Re p8806[32...53]:
Location identifier.
p8798[0...1] CAN speed conversion factor / n_conv_factor
VECTOR_G (CAN) Can be changed: T Calculated: - Access level: 3
Data type: Unsigned32 Dyn. index: - Func. diagram: -
P-Group: - Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
1 4294967295 1
p8805 Identification and maintenance 4 configuration / I&M 4 config
CU_G130_DP,
CU_G130_PN,
CU_G150_DP,
CU_G150_PN
Can be changed: U, T Calculated: - Access level: 3
Data type: Integer16 Dyn. index: - Func. diagram: -
P-Group: - Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 1 0
p8806[0...53] Identification and Maintenance 1 / I&M 1
CU_G130_DP,
CU_G130_PN,
CU_G150_DP,
CU_G150_PN
Can be changed: U, T Calculated: - Access level: 3
Data type: Unsigned8 Dyn. index: - Func. diagram: -
P-Group: - Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- -