2 Parameters
2.2 List of parameters
SINAMICS G130/G150
706 List Manual (LH2), 04/2014, A5E03263479A
Description: Displays the circulating current of phase V as peak value.
Description: Displays the circulating current of phase W as peak value.
Description: Ring buffer for faults and alarms that have occurred from power units connected in parallel (Motor Module, Active
Line Infeed, Voltage Sensing Module).
Displays the fault/alarm code.
Dependency: Refer to: r7101, r7102, r7103
Note: The last fault case that occurred is documented in index 0.
The parameter is reset to 0 at POWER ON.
Description: Ring buffer for faults and alarms that have occurred from power units connected in parallel (Motor Module, Active
Line Infeed, Voltage Sensing Module).
p7101 < 100:
Displays the Power unit Data Set number (PDS).
p7101 >= 100:
Displays the Voltage Sensing Module Data Set number (VSMDS)
Dependency: Refer to: r7100, r7102, r7103
Note: The last fault case that occurred is documented in index 0.
The parameter is reset to 0 at POWER ON.
r7051[0...n] Par_circuit circulating current phase V / Circ_I_phase V
VECTOR_G (Parallel) Can be changed: - Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: PDS, p0120 Func. diagram: -
P-Group: Displays, signals Units group: 6_5 Unit selection: p0505
Not for motor type: - Scaling: p2002 Expert list: 1
Min Max Factory setting
- [A] - [A] - [A]
r7052[0...n] Par_circuit circulating current phase W / Circ_I_phase W
VECTOR_G (Parallel) Can be changed: - Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: PDS, p0120 Func. diagram: -
P-Group: Displays, signals Units group: 6_5 Unit selection: p0505
Not for motor type: - Scaling: p2002 Expert list: 1
Min Max Factory setting
- [A] - [A] - [A]
r7100[0...99] Par_circuit ring buffer fault/alarm code / Fault/alarm code
B_INF (Parallel),
VECTOR_G (Parallel)
Can be changed: - Calculated: - Access level: 3
Data type: Unsigned32 Dyn. index: - Func. diagram: -
P-Group: Displays, signals Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
r7101[0...99] Par_circuit ring buffer data set number / Ring buffer Ds_no
B_INF (Parallel),
VECTOR_G (Parallel)
Can be changed: - Calculated: - Access level: 3
Data type: Unsigned32 Dyn. index: - Func. diagram: -
P-Group: Displays, signals Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -