Loading...
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
581
2 Parameters
2.2 List of parameters
Description: The friction characteristic is defined by 10 value pairs.
This parameter specifies the n coordinate of the 1st value pair of the friction characteristic.
Dependency: Refer to: p3830, p3845
Description: The friction characteristic is defined by 10 value pairs.
This parameter specifies the n coordinate of the 2nd value pair of the friction characteristic.
Dependency: Refer to: p3831, p3845
Description: The friction characteristic is defined by 10 value pairs.
This parameter specifies the n coordinate of the 3rd value pair of the friction characteristic.
Dependency: Refer to: p3832, p3845
Description: The friction characteristic is defined by 10 value pairs.
This parameter specifies the n coordinate of the 4th value pair of the friction characteristic.
Dependency: Refer to: p3833, p3845
p3820[0...n] Friction characteristic value n0 / Friction n0
VECTOR_G (n/M) Can be changed: T Calculated:
CALC_MOD_LIM_REF
Access level: 2
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 7010
P-Group: Functions Units group: 3_1 Unit selection: p0505
Not for motor type: REL Scaling: - Expert list: 1
Min Max Factory setting
0.00 [rpm] 210000.00 [rpm] 15.00 [rpm]
p3821[0...n] Friction characteristic value n1 / Friction n1
VECTOR_G (n/M) Can be changed: T Calculated:
CALC_MOD_LIM_REF
Access level: 2
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 7010
P-Group: Functions Units group: 3_1 Unit selection: p0505
Not for motor type: REL Scaling: - Expert list: 1
Min Max Factory setting
0.00 [rpm] 210000.00 [rpm] 30.00 [rpm]
p3822[0...n] Friction characteristic value n2 / Friction n2
VECTOR_G (n/M) Can be changed: T Calculated:
CALC_MOD_LIM_REF
Access level: 2
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 7010
P-Group: Functions Units group: 3_1 Unit selection: p0505
Not for motor type: REL Scaling: - Expert list: 1
Min Max Factory setting
0.00 [rpm] 210000.00 [rpm] 60.00 [rpm]
p3823[0...n] Friction characteristic value n3 / Friction n3
VECTOR_G (n/M) Can be changed: T Calculated:
CALC_MOD_LIM_REF
Access level: 2
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 7010
P-Group: Functions Units group: 3_1 Unit selection: p0505
Not for motor type: REL Scaling: - Expert list: 1
Min Max Factory setting
0.00 [rpm] 210000.00 [rpm] 120.00 [rpm]