Description: Display and connector output for the reference quantity for speed and frequency (p2000).
All speeds or frequencies specified as relative value are referred to this reference quantity.
The reference quantity corresponds to 100% or 4000 hex (word) or 4000 0000 hex (double word).
The following applies: Reference frequency (in Hz) = reference speed (in rpm) / 60
This parameter has the unit rpm.
Dependency: Refer to: p2000
Note: This BICO parameter provides the numerical value of the reference quantity p2000 as a connector output for
interconnection with Drive Control Chart (DCC). The numerical value can be adopted unchanged from this connector
output in DCC. This BICO parameter is not suitable for interconnecting for cyclic communication.
Description: Display and connector output for the actual reference quantity for velocity and frequency.
All velocities or frequencies specified as relative value are referred to this reference quantity.
The reference quantity corresponds to 100% or 4000 hex (word) or 4000 0000 hex (double word).
The following applies: Reference frequency (in Hz) = reference velocity (in m/min) / 60
Dependency: Refer to: p2000
Note: This BICO parameter provides the numerical value of the reference quantity p2000 as a connector output for
interconnection with Drive Control Chart (DCC). The numerical value can be adopted unchanged from this connector
output in DCC. This BICO parameter is not suitable for interconnecting for cyclic communication.
Description: Connector output of the reference quantity for voltages p2001.
All voltages specified as relative value are referred to this reference quantity.
The reference quantity corresponds to 100% or 4000 hex (word) or 4000 0000 hex (double word).
This parameter has the unit Vrms.
Dependency: Refer to: p2001
Note: This BICO parameter provides the numerical value of the reference quantity p2001 as a connector output for
interconnection with Drive Control Chart (DCC). The numerical value can be adopted unchanged from this connector
output in DCC. This BICO parameter is not suitable for interconnecting for cyclic communication.
r2700 CO: Reference speed/reference frequency / n_ref/f_ref
ENC, VECTOR_G Can be changed: - Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: - Func. diagram: -
P-Group: - Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
r2700 CO: Reference velocity/reference frequency actual / v_ref/f_ref act
ENC (Lin_enc) Can be changed: - Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: - Func. diagram: -
P-Group: - Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
r2701 CO: Reference voltage / Reference voltage
B_INF, VECTOR_G Can be changed: - Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: -
P-Group: - Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1