Description: Displays the status word for the motor holding brake.
Description: Sets the signal source to activate the armature short-circuit or DC braking.
Dependency: Refer to: p1231, p1232, p1233, p1234, p1235, p1236, p1237, r1238, r1239, p1345, p1346
Note: 1 signal: Armature short-circuit/DC braking activated.
0 signal: Armature short-circuit/DC braking de-activated.
Description: Setting to activate the various types for armature short-circuit / DC braking.
Value: 0: No function
1: External armature short-circuit with contactor feedback signal
2: Ext. armature short circuit without contactor feedback signal
3: Internal voltage protection
4: Internal armature short-circuit / DC braking
5: DC braking for OFF1/OFF3
14: DC braking below starting speed
Dependency: Refer to: p0300, p1230, p1232, p1233, p1234, p1235, p1236, p1237, r1238, r1239, p1345, p1346
r1229.1...11 CO/BO: Motor holding brake status word / Brake ZSW
VECTOR_G (Ext
brake)
Can be changed: - Calculated: - Access level: 2
Data type: Unsigned32 Dyn. index: - Func. diagram: -
P-Group: Functions Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
01 Command open brake (continuous signal) Yes No 2711
03 Pulse enable extended brake control Yes No 2711
04 Brake does not open Yes No 2711
05 Brake does not close Yes No 2711
06 Brake threshold exceeded Yes No 2707
07 Brake threshold undershot Yes No 2704
08 Brake monitoring time expired Yes No 2704
09 Pulse enable request missing/n_ctrl
inhibited
Yes No 2707
10 Brake OR logic operation result Yes No 2707
11 Brake AND logic operation result Yes No 2707
p1230[0...n] BI: Armature short-circuit / DC braking activation / ASC/DCBRK act
VECTOR_G Can be changed: U, T Calculated: - Access level: 1
Data type: Unsigned32 / Binary Dyn. index: CDS, p0170 Func. diagram: 7014, 7016,
7017
P-Group: Functions Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0
p1231[0...n] Armature short-circuit / DC braking configuration / ASC/DCBRK config
VECTOR_G Can be changed: U, T Calculated: - Access level: 1
Data type: Integer16 Dyn. index: MDS, p0130 Func. diagram: 7014, 7016,
7017
P-Group: Functions Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 14 0