2 Parameters
2.2 List of parameters
SINAMICS G130/G150
620 List Manual (LH2), 04/2014, A5E03263479A
The scaling characteristic for the analog outputs is defined using 2 points.
This parameter specifies the y coordinate (output voltage in V or output current in mA) of the 2nd value pair of the
characteristic.
Index: [0] = AO 0 (X522.1, X522.2, X522.3)
[1] = AO 1 (X522.4, X522.5, X522.6)
Dependency: The unit of this parameter (V or mA) depends on the analog output type.
Refer to: r4076, p4076
Notice: This parameter is automatically overwritten when changing p4076 (type of analog outputs).
Note: The parameters for the characteristic do not have a limiting effect.
Description: Sets the signal source for inverting the analog output signals of the Terminal Board 30 (TB30).
Index: [0] = AO 0 (X482.5/X482.6)
[1] = AO 1 (X482.7/X482.8)
Description: Sets the signal source to invert the analog output signals of Terminal Module 31 (TM31).
Index: [0] = AO 0 (X522.1, X522.2, X522.3)
[1] = AO 1 (X522.4, X522.5, X522.6)
Description: Sets the offset for the analog outputs of Terminal Board 30 (TB30).
The offset is added to the output signal after the scaling characteristic.
Index: [0] = AO 0 (X482.5/X482.6)
[1] = AO 1 (X482.7/X482.8)
Description: Sets the offset for the analog outputs of Terminal Module 31 (TM31).
The offset is added to the output signal after the scaling characteristic.
p4082[0...1] BI: TB30 analog outputs invert signal source / TB30 AO inv s s
TB30 Can be changed: U, T Calculated: - Access level: 3
Data type: Unsigned32 / Binary Dyn. index: - Func. diagram: 9106
P-Group: Terminals Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0
p4082[0...1] BI: TM31 analog outputs invert signal source / TM31 AO inv s s
TM31 Can be changed: U, T Calculated: - Access level: 3
Data type: Unsigned32 / Binary Dyn. index: - Func. diagram: 9572
P-Group: Terminals Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0
p4083[0...1] TB30 analog outputs offset / TB30 AO offset
TB30 Can be changed: U, T Calculated: - Access level: 1
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 9106
P-Group: Terminals Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
-10.000 10.000 0.000
p4083[0...1] TM31 analog outputs offset / TM31 AO offset
TM31 Can be changed: U, T Calculated: - Access level: 1
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 9572
P-Group: Terminals Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
-20.000 20.000 0.000