2 Parameters
2.2 List of parameters
SINAMICS G130/G150
216 List Manual (LH2), 04/2014, A5E03263479A
27: inch³/h
28: lb/s
29: lb/min
30: lb/h
31: lbf
32: lbf ft
Dependency: Only the unit of the technology controller parameters are switched over (unit group 9_1).
Refer to: p0596
Note: When switching over from % into another unit, the following sequence applies:
- set p0596
- set p0595 to the required unit
Description: Sets the reference quantity for the technological units.
When changing over using changeover parameter p0595 to absolute units, all of the parameters involved refer to the
reference quantity.
Dependency: Refer to: p0595
Notice: When changing over from one technological unit into another, or when changing the reference parameter, a
changeover is not made.
Description: Sets the sensor to monitor the motor temperature.
The sensor type used is set in p0601.
Value: 0: No sensor
1: Temperature sensor via encoder 1
2: Temperature sensor via encoder 2
3: Temperature sensor via encoder 3
10: Temperature sensor via a BICO interconnection
11: Temperature sensor via Motor Module / CU terminals
20: Temperature sensor via a BICO interconnection p0608
21: Temperature sensor via a BICO interconnection p0609
Dependency: Refer to: r0458, p0601, p0603
Caution: If, for a selected temperature sensor (p0600 > 0), the motor temperature sensor is not connected but another sensor,
then the temperature adaptation of the motor resistances must be switched out. Otherwise, in controlled-loop
operation, torque errors will occur that will mean that the drive will not be able to be stopped.
Notice: The parameter is calculated in the drive using p0340 and is inhibited for p0340 > 0.
For operation with a braking resistor (p1300 = 15), p0600 = 11 is automatically set when commissioning.
Note: Re p0600 = 0:
With induction motors, the motor temperature is calculated using the motor temperature model (see also p0612.1).
Re p0600 = 1, 2, 3:
Bimetallic switch (p0601 = 4) and PT100 temperature sensor (p0601 = 5) are not supported.
Re p0600 = 10:
The BICO interconnection should be executed via connector input p0603.
p0596 Technological unit reference quantity / Tech unit ref qty
VECTOR_G
(Tech_ctrl)
Can be changed: T Calculated: - Access level: 1
Data type: FloatingPoint32 Dyn. index: - Func. diagram: -
P-Group: - Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.01 340.28235E36 1.00
p0600[0...n] Motor temperature sensor for monitoring / Mot temp_sensor
VECTOR_G Can be changed: C2(3), U, T Calculated: CALC_MOD_ALL Access level: 2
Data type: Integer16 Dyn. index: MDS, p0130 Func. diagram: 8016
P-Group: Motor Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 21 0