SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
573
2 Parameters
2.2 List of parameters
Dependency: Refer to: p3665
Note: For sensor type PTC (p3665 = 1), the following applies:
- below the nominal response temperature, r3666 = -50°C.
- above the nominal response temperature, r3666 = 199.9 °C.
Description: Sets the alarm threshold for the KTY temperature sensor of the Voltage Sensing Module (VSM) to monitor the line
filter temperature.
Prerequisite:
A KTY84 sensor is connected and p3665 is set to 2.
Dependency: Refer to: p3665
Description: Sets the shutdown threshold for the KTY temperature sensor of the VSM to monitor the line filter temperature.
Dependency: Refer to: p3667
Description: Sets the hysteresis for the alarm threshold of the VSM to monitor the line filter temperature.
Dependency: Refer to: p3667
Description: Sets CT gain of the CT connected at the 10 V input of the Voltage Sensing Module (VSM).
The parameter specifies the current magnitude in [A] referred to the input voltage at the VSM in [V].
Example:
CT with 1 V per 200 A.
--> p3670 = 200
Dependency: Refer to: r3671, r3672
Note: The CT for phase 1 is connected at terminals X520.1 and X520.2 of the VSM.
The CT for phase 2 is connected at terminals X520.3 and X520.4 of the VSM.
p3667[0...n] VSM line filter overtemperature alarm threshold / VSMfilt_T A_thresh
VECTOR_G Can be changed: T Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: p0150 Func. diagram: 9886
P-Group: - Units group: 21_1 Unit selection: p0505
Not for motor type: - Scaling: p2006 Expert list: 1
Min Max Factory setting
-100.00 [°C] 301.00 [°C] 150.00 [°C]
p3668[0...n] VSM line filter overtemperature shutdown threshold / VSM filt_T F_thres
VECTOR_G Can be changed: T Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: p0150 Func. diagram: 9886
P-Group: - Units group: 21_1 Unit selection: p0505
Not for motor type: - Scaling: p2006 Expert list: 1
Min Max Factory setting
-100.00 [°C] 301.00 [°C] 180.00 [°C]
p3669[0...n] VSM line filter overtemperature hysteresis / VSM filt_T hyst
VECTOR_G Can be changed: T Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: p0150 Func. diagram: 9886
P-Group: - Units group: 21_2 Unit selection: p0505
Not for motor type: - Scaling: p2006 Expert list: 1
Min Max Factory setting
1.00 [K] 50.00 [K] 3.00 [K]
p3670[0...n] VSM 10 V input CT gain / VSM CT_gain
VECTOR_G Can be changed: T Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: p0150 Func. diagram: 9880
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: - Scaling: p2002 Expert list: 1
Min Max Factory setting
0.000 [A] 1000.000 [A] 1.000 [A]