2 Parameters
2.2 List of parameters
SINAMICS G130/G150
824 List Manual (LH2), 04/2014, A5E03263479A
Description: Sets the IP address for the onboard PROFINET interface on the Control Unit.
The active IP address is displayed in r8931.
Note: The interface configuration (p8920 and following) is activated with p8925.
The parameter is not influenced by setting the factory setting.
Description: Sets the default gateway for the onboard PROFINET interface on the Control Unit.
The active default gateway is displayed in r8932.
Note: The interface configuration (p8920 and following) is activated with p8925.
The parameter is not influenced by setting the factory setting.
Description: Sets the subnet mask for the onboard PROFINET interface on the Control Unit.
The active subnet mask is displayed in r8933.
Note: The interface configuration (p8920 and following) is activated with p8925.
The parameter is not influenced by setting the factory setting.
Description: Sets the DHCP mode for the onboard PROFINET interface on the Control Unit.
The active DHCP mode is displayed in r8934.
Notice: When the DHCP mode is active (p8924 > 0), then PROFINET communication via this interface is no longer possible!
However, the interface can be used by the STARTER/SCOUT commissioning tool.
Note: The interface configuration (p8920 and following) is activated with p8925.
The active DHCP mode is displayed in parameter r8934.
The parameter is not influenced by setting the factory setting.
If value = 0:
DHCP deactivated.
p8921[0...3] PN IP address of station / PN IP of stat
CU_G130_PN,
CU_G150_PN
Can be changed: U, T Calculated: - Access level: 3
Data type: Unsigned8 Dyn. index: - Func. diagram: -
P-Group: - Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 255 0
p8922[0...3] PN Default Gateway of Station / PN Def Gateway
CU_G130_PN,
CU_G150_PN
Can be changed: U, T Calculated: - Access level: 3
Data type: Unsigned8 Dyn. index: - Func. diagram: -
P-Group: - Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 255 0
p8923[0...3] PN Subnet Mask of Station / PN Subnet Mask
CU_G130_PN,
CU_G150_PN
Can be changed: U, T Calculated: - Access level: 3
Data type: Unsigned8 Dyn. index: - Func. diagram: -
P-Group: - Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 255 0
p8924 PN DHCP Mode / PN DHCP Mode
CU_G130_PN,
CU_G150_PN
Can be changed: U, T Calculated: - Access level: 3
Data type: Unsigned8 Dyn. index: - Func. diagram: -
P-Group: - Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 3 0