2 Parameters
2.2 List of parameters
Description: Sets the scaling characteristic for the analog outputs of Terminal Board 30 (TB30).
The scaling characteristic for the analog outputs is defined using 2 points.
This parameter specifies the x coordinate (percentage) of the 2nd value pair of the characteristic.
Index: [0] = AO 0 (X482.5/X482.6)
[1] = AO 1 (X482.7/X482.8)
Note: The parameters for the characteristic do not have a limiting effect.
Description: Sets the scaling characteristic for the analog outputs of Terminal Module 31 (TM31).
The scaling characteristic for the analog outputs is defined using 2 points.
This parameter specifies the x coordinate (percentage) of the 2nd value pair of the characteristic.
Index: [0] = AO 0 (X522.1, X522.2, X522.3)
[1] = AO 1 (X522.4, X522.5, X522.6)
Dependency: Refer to: r4076, p4076
Notice: This parameter is automatically overwritten when changing p4076 (type of analog outputs).
Note: The parameters for the characteristic do not have a limiting effect.
Description: Sets the scaling characteristic for the analog outputs of Terminal Board 30 (TB30).
The scaling characteristic for the analog outputs is defined using 2 points.
This parameter specifies the y coordinate (output voltage in V) of the 2nd value pair of the characteristic.
Index: [0] = AO 0 (X482.5/X482.6)
[1] = AO 1 (X482.7/X482.8)
Note: The parameters for the characteristic do not have a limiting effect.
Description: Sets the scaling characteristic for the analog outputs of Terminal Module 31 (TM31).
p4079[0...1] TB30 analog outputs characteristic value x2 / TB30 AO char x2
TB30 Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 9106
P-Group: Terminals Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
-1000.00 [%] 1000.00 [%] 100.00 [%]
p4079[0...1] TM31 analog outputs characteristic value x2 / TM31 AO char x2
TM31 Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 9572
P-Group: Terminals Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
-1000.00 [%] 1000.00 [%] 100.00 [%]
p4080[0...1] TB30 analog outputs characteristic value y2 / TB30 AO char y2
TB30 Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 9106
P-Group: Terminals Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
-11.000 [V] 11.000 [V] 10.000 [V]
p4080[0...1] TM31 analog outputs characteristic value y2 / TM31 AO char y2
TM31 Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 9572
P-Group: Terminals Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
-20.000 [V] 20.000 [V] 10.000 [V]