2 Parameters
2.2 List of parameters
SINAMICS G130/G150
236 List Manual (LH2), 04/2014, A5E03263479A
The binector inputs of the corresponding command data set are appropriately interconnected.
The selected macro file must be available on the memory card/device memory.
Example:
p0700 = 6 --> macro file PM000006.ACX is run.
Dependency: Refer to: p0015, p1000, p1500, r8571
Notice: No errors were issued during quick commissioning (p3900 = 1) when writing to parameters of the QUICK_IBN group!
When executing a specific macro, the corresponding programmed settings are made and become active.
Note: The macros in the specified directory are displayed in r8571. r8571 is not in the expert list of the commissioning
software.
Macros available as standard are described in the technical documentation of the particular product.
BI: Binector Input
CDS: Command Data Set
Description: Runs the corresponding macro files.
The selected macro file must be available on the memory card/device memory.
Example:
p0700 = 6 --> macro file PM000006.ACX is run.
Dependency: Refer to: r8571
Notice: No errors were issued during quick commissioning (p3900 = 1) when writing to parameters of the QUICK_IBN group!
When executing a specific macro, the corresponding programmed settings are made and become active.
Note: The macros in the specified directory are displayed in r8571. r8571 is not in the expert list of the commissioning
software.
Macros available as standard are described in the technical documentation of the particular product.
BI: Binector Input
CDS: Command Data Set
Description: Displays the actual value at the digital inputs.
This means that the actual input signal can be checked at terminal DI x or DI/DO x prior to switching from the
simulation mode (p0795.x = 1) to terminal mode (p0795.x = 0).
p0700 Macro Binector Input (BI) for TMs / Macro BI TM
TB30, TM31 Can be changed: C2(1), T Calculated: - Access level: 1
Data type: Unsigned32 Dyn. index: - Func. diagram: -
P-Group: Commands Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 999999 0
r0721 CU digital inputs terminal actual value / CU DI term act val
CU_G130_DP,
CU_G130_PN,
CU_G150_DP,
CU_G150_PN
Can be changed: - Calculated: - Access level: 2
Data type: Unsigned32 Dyn. index: - Func. diagram: 2020, 2030,
2031, 2100, 2119, 2120, 2130,
2131, 2132, 2133
P-Group: Commands Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 DI 0 (X122.1/X121.1) High Low -
01 DI 1 (X122.2/X121.2) High Low -
02 DI 2 (X122.3/X121.3) High Low -
03 DI 3 (X122.4/X121.4) High Low -
04 DI 4 (X132.1 / -) High Low -
05 DI 5 (X132.2 / -) High Low -
06 DI 6 (X132.3 / -) High Low -
07 DI 7 (X132.4 / -) High Low -
08 DI/DO 8 (X122.9/X121.7) High Low -
09 DI/DO 9 (X122.10/X121.8) High Low -