2 Parameters
2.2 List of parameters
Re p0600 = 11:
For SINAMICS S120 AC Drive (AC/AC) and using the Control Unit Adapter CUA31, the temperature sensor is
connected at the adapter (X210).
Re p0600 = 20, 21:
The BICO interconnection should be executed via connector input p0608 or p0609.
Associated parameters: p0601, p4600 ... p4603, p4610 ... p4613
Description: Sets the sensor type for the temperature measurement at input X21 (booksize) or X41 (chassis).
The measured value is displayed in r0035.
Value: 0: No sensor
1: PTC alarm & timer
2: KTY84
4: Bimetallic NC contact alarm & timer
Dependency: Refer to: r0035
Note: The measured value display depends on the selected sensor type.
Re p0601 = 0:
--> r0035 = -200 °C
Re p0601 = 1:
Tripping resistance = 1650 Ohm (lower resistance --> r0035 = -50 °C, higher resistance --> r0035 = 250 °C).
Re p0601 = 2:
Displays the temperature in °C.
Re p0601 = 4:
r0035 = -50 °C
--> The tripping resistance is less than 100 Ohm (bimetallic NC contact is closed or has a short-circuit).
r0035 = 250 °C
--> The tripping resistance is greater than 100 Ohm (bimetallic NC contact is open, not connected or has a wire
breakage).
When using the following components, a value of 4 is set as the factory setting and can no longer be changed:
- Basic Line Module (BLM) with internal Braking Module.
- Active Line Module (ALM) with line filter Active Interface Module (AIM, p0220[0] = 41 ... 45).
In these cases, in addition to the temperature display, the temperature is also monitored.
Description: Sets the sensor type for the motor temperature monitoring.
Value: 0: No sensor
1: PTC alarm & timer
2: KTY84
3: KTY84 and PTC (only for motors with DRIVE-CLiQ):
4: Bimetallic NC contact alarm & timer (only for temp_eval via MM)
5: PT100
10: Evaluation via several temperature channels SME12x
11: Evaluation via several temperature channels BICO
p0601 Temperature sensor, sensor type / Temp_sens type
B_INF Can be changed: C2(3), U, T Calculated: - Access level: 2
Data type: Integer16 Dyn. index: - Func. diagram: -
P-Group: Motor Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 4 0
p0601[0...n] Motor temperature sensor type / Mot_temp_sens type
VECTOR_G Can be changed: C2(3), U, T Calculated: - Access level: 2
Data type: Integer16 Dyn. index: MDS, p0130 Func. diagram: 8016
P-Group: Motor Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 11 2