EasyManua.ls Logo

Siemens SINAMICS G150 - BI: ESM Direction of Rotation Signal Source; ESM Rot dir S S; CI: ESM Setpoint TB30;TM31 Analog Input; ESM Setp TB30 TM31; ESM Number of Activations;Faults; ESM Act;Fault Qty; ESM Reset Number of Activations;Faults; ESM Act;F Qty R

Siemens SINAMICS G150
1842 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2 Parameters
2.2 List of parameters
SINAMICS G130/G150
592 List Manual (LH2), 04/2014, A5E03263479A
Description: Sets the signal source for the direction of rotation during essential service mode (ESM).
p3883 = 1 signal:
Direction of rotation of the setpoint, parameterized for essential service mode, is reversed.
p3883 = 0 signal:
Direction of rotation of the setpoint parameterized for essential service mode is kept.
Note: ESM: Essential Service Mode
Description: Sets the signal source for the setpoint for p3881 = 5 (TB30/TM31 analog input) in the essential service mode (ESM).
Dependency: Refer to: p3881
Note: ESM: Essential Service Mode
Description: Displays the number of activations and faults that have occurred for the essential service mode (ESM).
Index: [0] = Activation of the essential service mode
[1] = Faults during the essential service mode
Dependency: Refer to: p3888
Note: ESM: Essential Service Mode
Description: Setting to reset the number of activations and faults that have occurred for the essential service mode (ESM).
1: counter reset active (r3887[0, 1])
0: inactive
Dependency: Refer to: r3887
Note: ESM: Essential Service Mode
The parameter is automatically reset to zero after the counter has been reset.
p3883 BI: ESM direction of rotation signal source / ESM rot dir s s
VECTOR_G Can be changed: T Calculated: - Access level: 3
Data type: Unsigned32 / Binary Dyn. index: - Func. diagram: 7033
P-Group: Functions Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0
p3886 CI: ESM setpoint TB30/TM31 analog input / ESM setp TB30TM31
VECTOR_G Can be changed: U, T Calculated: - Access level: 3
Data type: Unsigned32 / FloatingPoint32 Dyn. index: - Func. diagram: 7033
P-Group: Functions Units group: - Unit selection: -
Not for motor type: - Scaling: p2000 Expert list: 1
Min Max Factory setting
- - 0
r3887[0...1] ESM number of activations/faults / ESM act/fault qty
VECTOR_G Can be changed: - Calculated: - Access level: 4
Data type: Unsigned16 Dyn. index: - Func. diagram: 7033
P-Group: Functions Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
p3888 ESM reset number of activations/faults / ESM act/F qty r
VECTOR_G Can be changed: T Calculated: - Access level: 4
Data type: Unsigned8 Dyn. index: - Func. diagram: 7033
P-Group: Functions Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 1 0