2 Parameters
2.2 List of parameters
SINAMICS G130/G150
114 List Manual (LH2), 04/2014, A5E03263479A
Description: Sets the run-up time of the cooling unit after a power-off command.
Description: Displays the control word for the cooling unit.
Description: Sets the signal sources for the feedback signals from the cooling unit.
Index: [0] = Cooling unit powered up
[1] = Cooling unit ready to be powered up
[2] = Cooling unit no alarm present
[3] = Cooling unit no fault present
[4] = Cooling unit no leaked liquid
[5] = Cooling unit liquid flow OK
[6] = Cooling unit conductivity < fault threshold
[7] = Cooling unit conductivity < alarm threshold
Description: Displays the status word of the cooling unit.
p0264 Cooling unit run-on time / RKA run-on time
B_INF (Cool_unit),
VECTOR_G
(Cool_unit)
Can be changed: U, T Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 9795
P-Group: Converter Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.0 [s] 180.0 [s] 30.0 [s]
r0265.0...3 BO: Cooling unit control word / RKA STW
B_INF (Cool_unit),
VECTOR_G
(Cool_unit)
Can be changed: - Calculated: - Access level: 3
Data type: Unsigned8 Dyn. index: - Func. diagram: -
P-Group: Commands Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Power up cooling unit Activating De-activating -
01 Message converter off OFF ON -
02 Acknowledge faults Acknowledgement No acknowledgement -
03 Leakage sensing OK No leaked liquid Leaked liquid -
p0266[0...7] BI: Cooling unit feedback signals signal source / RKA fdbk S_src
B_INF (Cool_unit),
VECTOR_G
(Cool_unit)
Can be changed: U, T Calculated: - Access level: 3
Data type: Unsigned32 / Binary Dyn. index: - Func. diagram: -
P-Group: Communications Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 1
r0267.0...7 BO: Cooling unit status word / RKA ZSW
B_INF (Cool_unit),
VECTOR_G
(Cool_unit)
Can be changed: - Calculated: - Access level: 3
Data type: Unsigned16 Dyn. index: - Func. diagram: -
P-Group: Commands Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 RKA powered up Yes No -
01 RKA ready to be powered up Yes No -
02 RKA no alarm present Yes No -
03 RKA no fault present Yes No -
04 RKA no leaked fluid Yes No -