2 Parameters
2.2 List of parameters
SINAMICS G130/G150
126 List Manual (LH2), 04/2014, A5E03263479A
Description: Sets the maximum motor speed.
Dependency: Refer to: p1082
Notice: When selecting a catalog motor (p0301), this parameter is automatically pre-assigned and is write protected.
Information in p0300 should be carefully observed when removing write protection.
If p0322 is changed during quick commissioning (p0010 = 1), the maximum speed p1082, which is also associated
with quick commissioning, is pre-assigned accordingly. This is not the case when commissioning the motor (p0010 =
3).
Note: The parameter has no significance for a value of p0322 = 0.
Description: Sets the maximum permissible motor current (e.g. de-magnetizing current for synchronous motors).
Notice: When selecting a catalog motor (p0301), this parameter is automatically pre-assigned and is write protected.
Information in p0300 should be carefully observed when removing write protection.
If p0323 is changed during quick commissioning (p0010 = 1), then the maximum current p0640 is pre-assigned
accordingly. This is not the case when commissioning the motor (p0010 = 3).
Note: The parameter has no effect for induction motors.
The parameter has not effect for synchronous motors if a value of 0.0 is entered. The user-selectable current limit is
entered into p0640.
Description: Sets the maximum speed for the winding.
The following applies when calculating the maximum speed (p1082):
- for p0324 = 0 or p0532 = 0, p0322 is used.
- for p0324 > 0 and p0532 > 0, the minimum value from the two parameters is used.
Dependency: Refer to: p0322, p0532, p1082
Notice: When selecting a catalog motor (p0301), this parameter is automatically pre-assigned and is write protected.
Information in p0300 should be carefully observed when removing write protection.
If p0324 is changed during quick commissioning (p0010 = 1), then the maximum speed p1082, which is also
associated with quick commissioning, is pre-assigned appropriately. This is not the case when commissioning the
motor (p0010 = 3).
p0322[0...n] Maximum motor speed / Mot n_max
VECTOR_G Can be changed: C2(1, 3) Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: MDS, p0130 Func. diagram: -
P-Group: Motor Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.0 [rpm] 210000.0 [rpm] 0.0 [rpm]
p0323[0...n] Maximum motor current / Mot I_max
VECTOR_G Can be changed: C2(1, 3) Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: MDS, p0130 Func. diagram: -
P-Group: Motor Units group: - Unit selection: -
Not for motor type: ASM, FEM Scaling: - Expert list: 1
Min Max Factory setting
0.00 [Arms] 20000.00 [Arms] 0.00 [Arms]
p0324[0...n] Winding maximum speed / Winding n_max
VECTOR_G Can be changed: C2(1, 3) Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: MDS, p0130 Func. diagram: -
P-Group: Motor Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.0 [rpm] 210000.0 [rpm] 0.0 [rpm]