SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
247
2 Parameters
2.2 List of parameters
Dependency: The setpoint for the input signals is specified using p0796.
Refer to: p0796, p9620
Notice: If a digital input is used as signal source for the function "STO" (BI: p9620) then it is not permissible to select the
simulation mode and this is rejected.
To the terminal designation:
The first designation stands for CU320, the second for CU310.
Note: This parameter is not saved when data is backed-up (p0971, p0977).
DI: Digital Input
DI/DO: Bidirectional Digital Input/Output
Description: Sets the setpoint for the input signals in the digital input simulation mode.
Bit field: Bit Signal name 1 signal 0 signal FP
00 DI 0 (X122.1/X121.1) Simulation Terminal eval -
01 DI 1 (X122.2/X121.2) Simulation Terminal eval -
02 DI 2 (X122.3/X121.3) Simulation Terminal eval -
03 DI 3 (X122.4/X121.4) Simulation Terminal eval -
04 DI 4 (X132.1 / -) Simulation Terminal eval -
05 DI 5 (X132.2 / -) Simulation Terminal eval -
06 DI 6 (X132.3 / -) Simulation Terminal eval -
07 DI 7 (X132.4 / -) Simulation Terminal eval -
08 DI/DO 8 (X122.9/X121.7) Simulation Terminal eval -
09 DI/DO 9 (X122.10/X121.8) Simulation Terminal eval -
10 DI/DO 10 (X122.12/X121.10) Simulation Terminal eval -
11 DI/DO 11 (X122.13/X121.11) Simulation Terminal eval -
12 DI/DO 12 (X132.9/X131.1) Simulation Terminal eval -
13 DI/DO 13 (X132.10/X131.2) Simulation Terminal eval -
14 DI/DO 14 (X132.12/X131.4) Simulation Terminal eval -
15 DI/DO 15 (X132.13/X131.5) Simulation Terminal eval -
16 DI 16 (X122.5/X120.3) Simulation Terminal eval -
17 DI 17 (X122.6/X120.4) Simulation Terminal eval -
20 DI 20 (X132.5/X120.9) Simulation Terminal eval -
21 DI 21 (X132.6/X120.10) Simulation Terminal eval -
p0796 CU digital inputs simulation mode setpoint / CU DI simul setp
CU_G130_DP,
CU_G130_PN,
CU_G150_DP,
CU_G150_PN
Can be changed: U, T Calculated: - Access level: 2
Data type: Unsigned32 Dyn. index: - Func. diagram: 2020, 2030,
2031, 2100, 2119, 2120, 2130,
2131, 2132, 2133
P-Group: Commands Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0000 0000 0000 0000 0000
0000 0000 0000 bin
Bit field: Bit Signal name 1 signal 0 signal FP
00 DI 0 (X122.1/X121.1) High Low -
01 DI 1 (X122.2/X121.2) High Low -
02 DI 2 (X122.3/X121.3) High Low -
03 DI 3 (X122.4/X121.4) High Low -
04 DI 4 (X132.1 / -) High Low -
05 DI 5 (X132.2 / -) High Low -
06 DI 6 (X132.3 / -) High Low -
07 DI 7 (X132.4 / -) High Low -
08 DI/DO 8 (X122.9/X121.7) High Low -
09 DI/DO 9 (X122.10/X121.8) High Low -
10 DI/DO 10 (X122.12/X121.10) High Low -
11 DI/DO 11 (X122.13/X121.11) High Low -
12 DI/DO 12 (X132.9/X131.1) High Low -
13 DI/DO 13 (X132.10/X131.2) High Low -
14 DI/DO 14 (X132.12/X131.4) High Low -
15 DI/DO 15 (X132.13/X131.5) High Low -
16 DI 16 (X122.5/X120.3) High Low -
17 DI 17 (X122.6/X120.4) High Low -