Fig. 3-12 2381 – Control commands / interrogation commands
- 2381 -
Function diagram
87654321
fp_2381_54_eng.vsd
DO: A_INF, B_INF, SERVO, S_INF, VECTOR
S120/S150/G130/G150
09.04.13 V04.07.00
PROFIenergy - Control commands/interrogation commands
Port 1
Port 2
PROFINET
START_Pause
END_Pause
&
PROFIenergy control commands
START_Pause with time response
Pause_Time
1
0
min max
+ Time_to_pause
+ Time_to_operate
[2382]
r5600 = 255
r5600 = 2
Time_to_pause Time_to_operate
PROFIenergy interrogation commands
"List_Energy_Saving_Modes
"Get_Mode
"PEM_Status
"PE_Identify
"Query_Version
"Get_Measurement_List
"Get_Measurement_Values
"Get_Measurement_Values_with_object_number
"Get_Measurement_List_with_object_number
"PEM_Status_with_CTTO
p5602
p5602 p5606
Ready for operation
Energy-saving mode 2
1 = Inhibit
PROFIenergy
5611.0