Fig. 3-70 2634 – Missing enable signals, line contactor control, logic operation
- 2634 -
Function diagram
87654321
fp_2634_54_eng.vsd
DO: SERVO, VECTOR
S120/S150/G130/G150
22.01.14 V04.07.00
Sequence control - Missing enable signals, line contactor control, logic operation
+24 V
Control Unit
Line contactor control
T
p0861
Time monitoring
&
F07300
"Line contactor
feedback signal
missing"
[2120]...[2133]
DI
DO
[2130]...[2133]
r0863.1
Line contactor feedback signal
p0860
Energize line contactor
r0863.1
Missing enable signals that prevent the drive going into operation
(this situation can be detected at the ZSW sequence control, infeed r0899.2 = 1 [8926] <5>)
Missing enable signals
1
To the infeed
&
1
Operating monitoring
ON/OFF monitoring
0
From the line
supply
p0115[3] (2000.00 μs)
<1> Only for VECTOR.
<2> For AC/AC devices, diode infeed
<3> Only for SINAMICS S120/G150.
<2>
<1>
1 = OFF2, enable missing1
2
3
5
9
1 = OFF1, enable missing
Bedeutung
1 = OFF3, enable missing
1 = Enable operation missing
1 = STOP2, enable missing
1 = Infeed, enable missing
Bit Nr.
0
10
11
12
1 = Ramp-function generator enable missing
1 = Ramp-function generator start missing
1 = Setpoint, enable missing
16
17
18
1 = OFF1, enable, internal missing
1 = OFF2, enable, internal missing
1 = OFF3, enable, internal missing
26 1 = Drive inactive or not operational
19 1 = Pulse enable, internal missing
25 1 = Function bypass active
27 1 = De-magnetization not completed
28 1 = Open brake missing
4 1 = Armature short-circuit/DC braking, enable missing
8 1 = Safety, enable missing
20
21
1 = Internal armature short circuit/DC braking, enable missing
1 = STOP2, enable internal missing
29
30
31
1 = Cooling system ready missing
1 = Jog setpoint active
1 = Speed controller inhibited
[2701.8]
[2610.4]<2>
[8732.4]<3>
[8832.4]<4>
[8932.4]<5>
Line contactor control from sequence control
1
r0046
Missing enable sig
[3020.5]
r0046.0
r0046.1
r0046.2
r0046.3
r0046.5
r0046.9
r0046.10
r0046.11
r0046.12
r0046.8
r0046.16
r0046.17
r0046.18
r0046.19
r0046.20
r0046.25
r0046.26
r0046.27
r0046.28
r0046.29
r0046.30
r0046.31
r0046.21
r0046.4
1
Fault with
OFF3 response
[3060.2]
[3060.4]
[3070.2]
[3070.4]
1 = Internal RFG missing
[3060.2]
[3070.2]
0 = Internal fast stop
(0)
p2810[1]
(0)
p2816[0]
(0)
p2816[1]
(0)
Logic operation
p2810[0]
AND operation
r2811.0
OR operation
r2817.0
<4> Only for SINAMICS S120.
<5> Only for SINAMICS S120/S150.
15 1 = QuickStop, enable missing r0046.15
r0046.12