Fig. 3-111 3060 â Basic ramp-function generator
- 3060 -
Function diagram
87654321
fp_3060_51_eng.vsd
DO: SERVO, VECTOR, VECTOR3P, VECTORGL, VECTORM2C, VECTORMV, VECTORSL
SINAMICS
16.01.14 V04.07.00
Setpoint channel - Basic ramp-function generator
OFF3 ramp-down time
0.000...600.000 [s]
p1135[D](0.000)
x
t
y
t
p1082
-p1082
x
p1082
-p1082
Tup Tdn
Tup Tdn
[3050.8]
y
0
0
0
0
[2634.4]
T
up
T
dn
r1119
RFG setpt at input
RFG tolerance for
ramp-up/ramp-down active
0.000...1000.000 [rpm]
p1148[D] (19.800)
0
1
x
y
[3050.5]
[3095.7]
n_max
p1082
From the setpoint limiting
Freeze ramp-function generator
[3080.1]
10
1 0
0
1
1
0
0
1
10
0 = Freeze ramp-function generator
r0898.5
1 = Enable speed setpoint
r0898.6
+
î
[2634.4]
1 = Enable ramp-function generator
r0898.4
Ramp-function generator, status bits
[3080.5]
0 = Internal fast stop
0 = Internal fast stop
Other status bits
Ramp-up active
Ramp-down active
n_set_4
[2501.3]
p1140
[2501.3]
p1141
[2501.3]
p1142
[3080.8]
Ramp flattening-off
p0115[3]
<101>
1 = Internal RFG enable
[2634.4]
1 = Bypass ramp-function generator
r1198.15[2505.3]
p1122
RFG setting value
(0)
p1144[C]
(0)
Accept RFG set val
p1143[C]
0
1
0
1
<1>
<1> For SERVO and VECTOR, the following applies: Inhibited during jogging.
<2> Only for SINAMICS S120.
<3> After a 0/1 signal a ramp-up is started again.
<4> With simultaneous jog 1 and 2 (p1055 = p1056 = 1) the last setpoint
remains effective (Freeze ramp-function generator).
<100> For SERVO, the following applies: Only if the function module
"Extended setpoint channel" is activated (r0108.8 = 1).
<101> To view the pre-assignment of the sampling times in p0115, refer to p0112.
<100>
r1149
RFG acceleration
<2>
<3>
<4>
RFG ramp-up time
0.000...999 999.000 [s]
p1120[D] (10.000)
RFG ramp-down time
0.000...999 999.000 [s]
p1121[D] (10.000)
Up ramp scaling
(1)
p1138[C]
Down ramp scaling
(1)
p1138[C]