Fig. 3-145 7017 â DC brake (p0300 = 1xx)
- 7017 -
Function diagram
87654321
fp_7017_54_eng.vsd
DO: SERVO, VECTOR
S120/S150/G130/G150
01.04.11 V04.07.00
Technology functions - DC brake (p0300 = 1xx)
The parameters of the I_max current controller are also used.
To pulse disable
To sequencer
MIN
î
Current actual values
<5> [5730]
<6> [6714]
Kp Tn
p0115
r1239.10
DC braking ready
n_set
BICO = 1
p0347
BICO = 0
n_set
p1234
p1233
p1232
p0347
Pulse inhibit
<3>
Braking response
p1232
<1>
ASC/DCBRK config
0...14
p1231[M] (0)
(0)
ASC/DCBRK act
p1230[C]
<4>
I_max_U_ctrl Kp
0.000...100000.000
p1345[D] (0.000)
I_max_U_ctrl Tn
0.000...50.000 [s]
p1346D] (0.030)
From I
2
t control
[8014]
|I_set|
|I_set|
t
t
|I_set|
n_act
n_act
t
|I_act|
To control [5730] <5>
[6730] <6>
To U/f-characteristic [6300] <6>
Pulse inhibit
<5>
t
+
<2>
|I_act|
n_set
p0347
p1232
|I_set|
n_act
t
Pulse inhibit
t
|I_act|
p1234
<8>
<6> Only for SINAMICS S120 and VECTOR.
<7> Only for VECTOR.
<8> DC brake upon falling below the starting speed for DC brake (p1234).
0
4,5,14
p1231 = 4
OFF1/OFF3
4,14
5
0
DC braking
not about BICO
1
p1231 = 5
p1231 = 14
<3>
<5>
<7> <7>
DCBRK I_brake
0.00...10000.00 [A]
p1232[M] (0.00)
DCBRK time
0.0...3600.0 [s]
p1233[M] (0.0)
DCBRK n_start
20.00...210000.00 [1/min]
p1234[M] (0.00)
Mot t_de-excitat
0.000...20.000 [s]
p0347[M] (0.000)
r0072
U_output
<1> The DC brake current is determined during automatic calculation (p0340 = 1).
<2> The de-magnetization time is determined during automatic calculation (p0340 = 1, 3).
<3> As soon as the standstill threshold (p1226) has been reached, the DC current injection will be aborted prematurely.
<4> Signal r1239.8 is only set while the DC brake is active.
<5> Only for SINAMICS S120 and SERVO.
DC braking active
r1239.8
I_ctrl Kp
0.000...100000.000 [V/A]
p1715[D] (0.000)
I_ctrl Tn
0.00...1000.00 [ms]
p1717[D] (2.00)
DC braking fault response
OFF
r0068[0]
I_act abs val