1195
3 Function diagrams
3.15 Technology functions
Fig. 3-147 7033 – Essential service mode (ESM)
- 7033 -
Function diagram
87654321
fp_7033_56_eng.vsd
DO: VECTOR
SINAMICS G130/G150
17.07.13 V04.07.00
Technology functions - Essential Service Mode (ESM)
p0115[0]
1 = Essential service mode (ESM) active
r3889.0 (0)
ESM rot dir S_src
p3883
1 = Direction of rotation inverted
r3889.1
r3887[0]
r3887[1]
Counter
Number of activations
Number of faults
ESM act/flts reset
p3888
[3040.6]
x1
x2
TM31/TB30 failure
ESM setp src
p3881 (0)
n_set_fixed 15 [rpm]
p1015 [D] (0.000)
-1
-1
-1
-1
ESM setp TB30TM31
(0)
p3886
1 = Setpoint signal lost
r3889.2
0
1
2
ESM setp altern
p3882 (0)
n_set_fixed 15 [rpm]
p1015 [D] (0.000)
n_max [rpm]
p1082 [D] (1500.000)
r2050[1]
PZD recv word, PZD 2
Setpoint failure
r2043.0
n_ref f_ref
p2000
&
&
OC/OFF2
r0898.1
1 = OFF1/OFF2 reaction activated
r3889.9
&
&
1
1
0
1
0
ON/OFF1
r0898.0
&
[3010.5]
[3010.5]
[3050.6]
1
0
1
0
1
0
1
0
[2468.5]
Speed setpoint
Essential service
mode
1
100
2x1x •
hex4000
2000p
10 s
r1078
Total setpoint eff
[rpm]
1
0
[3030.5]
ESM status word
r3889.0
r3889
r3889.1
r3889.2
r3889.7
r3889.8
r3889.9
(0)
ON/OFF (OFF1)
p0840[C]
(1)
OFF2 S_src 1
p0844[C]
(1)
OFF2 S_src 2
p0845[C]
< 6
7
6
1
3
0
5
> 5
<1> ESM can only be activated with
vector control or U/f control (p1300).
<1>
Last known
setpoint
(0)
ESM act S_src
p3880