EasyManua.ls Logo

Siemens SINAMICS G150 - Page 1209

Siemens SINAMICS G150
1842 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
1209
3 Function diagrams
3.17 Signals and monitoring functions
Fig. 3-159 8016 – Thermal monitoring, motor
- 8016 -
Function diagram
87654321
fp_8016_54_eng.vsd
DO: SERVO, VECTOR
S120/S150/G130/G150
28.01.14 V04.07.00
Signals and monitoring functions - Thermal monitoring, motor
Mot_temp_sens type
p0601[M]
Mot temp_sensor
p0600[M]
48 ms
r0035
Mot_temp
T0
&
&
Mod 2/KTY t_timer
p0606[M]
A07910
"Motor overtemperature"
F07011
"Motor overtemperature"
<1>
Fault response
I_max reduction
[6300.1], [6640.2]
Mot temp response
p0610[M]
p0610 = 1
Suppress fault
at p0610 = 0
[2548.2]
r2135.14
A07820 "Temperature sensor not connected"
A07015
"Motor temperature
sensor fault alarm"
A07016
"Motor temperature
sensor fault, fault"
-140 °C 250 °C
Sensor fault time
p0607[M]
<2>
0
1
Mod 1/2 threshold
p0605[M]
&
KTY sensor type
(threshold not applicable for PTC)
<4>
1
1
[2548.2]r2135.12
T0
<5>
KTY PTC
Sensor type
Mod 2/KTY A thresh
p0604[M]
0
1
<3>
M I N
Mot temp alarm 1
p0616[M]
<8>
1650
1
MAX
1
<1> For KTY, PT100, PT1000 and PTC, the value p0606 = 0 has a different meaning:
KTY, PT100, PT1000: 0 The output of the timer is always switched out (logical 0)
PTC: 0 Delay time = 0 s
<2> The switch-in delay p0607 = 0 suppresses fault F07016.
<3> For KTY, PT100, PT1000 and "No sensor", temperature as defined in the model.
<4> Applies only for VECTOR.
<5> p0606 does not work for alarms via p0616.
<6> p0601 = 5 can only be evaluated if r0192.15 = 1 and p0600 = 11; PT100 is calibrated via p0624.
<7> The assignment of temperature channels 1  4 depends on the hardware used.
<8> The relevant rated response temperature (°C) depends on the temperature sensor chosen by the motor manufacturer.
e.g. r4105 from TM31
[8017.8]
1
Mot Temperatur [°C]
(0)
p0603
[4704.8]
from Motor Modules
or CUA31
von Geber 3
[4704.8]
from encoder 1
[4704.8]
10 = Evaluation
across several
temperature
channels
SME12x
[9576.7]
0
1
2
3
11
10
from encoder 2
2 = KTY84
4 = Bimetal NC
contact alarm
with time step
for MM only
5 = PT100
<6>
11 = Evaluation
across several
temperature
channels BICO
Mot temperatur [°C]
(0)
p0608[0...3]
Mot temperatur [°C]
(0)
p0609[0...3]
20
21
0 = No sensor
3 = KTY84 & PTC,
for encoder only
1 = PTC alarm and
time
Mot Temp_sensortyp
Temp_sens type
p4603[E]
r4620[0] r4620[1] r4620[2] r4620[3]
p4600[E] p4601[E] p4602[E]
12
34
Temperature channel
Mot Temp_sensortyp
Temp sens type MDS
p4613[M]
r4620[0] r4620[1] r4620[2] r4620[3]
p4610[M] p4611[M] p4612[M]
12
34
Temperature channel
30 = Bimetal NC contact fault
12 = PTC alarm and time step
32 = Bimetal NC contact
alarm & time step
31 = Bimetal NC contact alarm
0 = No sensor
11 = PTC alarm
Configuration
10 = PTC fault
20 = KTY, PT100, PT1000
<7>
e.g. r4105 from TM120
e.g. r4105 from TM120
[8017.1]
only for KTY
[8017.8]
from mot temp module 1
[8017.8]

Table of Contents

Other manuals for Siemens SINAMICS G150

Related product manuals