SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
1213
3 Function diagrams
3.18 Diagnostics
Fig. 3-162 8060 – Fault buffer
- 8060 -
Function diagram
87654321
fp_8060_51_eng.vsd
DO: All objects
SINAMICS
19.02.14 V04.07.00
Diagnostics - Fault buffer
Fault responses to the sequence control [2610]
Fault presentr2139.3
[2548.2]
<1> This fault is overwritten when "more recent" faults occur (with the exception of "safety faults").
<2> The buffer parameters are cyclically updated in the background (refer to the status signal in r2139).
Actual
fault case
Fault 1
Fault 2
Fault 8
RESET
Fault case
comes
Fault case
count
p0952
p0952 = 0:
Fault buffer
delated
Delete fault buffer
r0945 = 0
r0947 = 0
r0948 = 0
r0949 = 0
r2109 = 0
r2130 = 0
r2133 = 0
r2136 = 0
r3115 = 0
r3120 = 0
r3122 = 0
Automatic
7. Acknow-
ledged
fault case
[oldest]
1. Acknow-
ledged
fault case
Fault buffer change [8065.6]
16 bit counter
LED "RDY" [= red for fault]
r2131
Fault code act
0 = "No fault present"
III
RESET
III
RESET
III
32 bit counter,
free running
1 ms
16 bit counter,
free running
POWER ON
[8065.1]
Operating time
Acknowledge faults
r2138.7
External fault 1
r2138.13
External fault 2
r2138.14
External fault 3
r2138.15
1
Background
p2102 ... p2105
[2546.3]
p2106
[2546.3]
p2107
[2546.1]
p2108, p3110 ... p3112
Faults ackn DO
p3981
Fault code
Fault 1
Fault 2
Fault 8
r0949[63] [I32]
r2133[63] [Float]
Fault 1
Fault 2
Fault 8
r0945[0]
r0947[0]
0945[1]
0947[1]
r0945[56]
r0947[56]
r0945[63]
r0947[63]
r0945[8]
r0947[8]
r0945[9]
r0947[9]
r0945[15]
r0947[15]
Fault value
r0949[0] [I32]
r2133[0] [Float]
r0949[1] [I32]
r2133[1] [Float]
r0949[7] [I32]
r2133[7] [Float]
r0949[56] [I32]
r2133[56] [Float]
r0949[57] [I32]
r2133[57] [Float]
r0949[8] [I32]
r2133[8] [Float]
r0949[9] [I32]
r2133[9] [Float]
r0949[15] [I32]
r2133[15] [Float]
Fault time
"come"
r0948[0] [ms]
r2130[0] [d]
r0948[1] [ms]
r2130[1] [d]
r0948[7] [ms]
r2130[7] [d]
r0948[56] [ms]
r2130[56] [d]
r0948[57] [ms]
r2130[57] [d]
r0948[63] [ms]
r2130[63] [d]
r0948[8] [ms]
r2130[8] [d]
r0948[9] [ms]
r2130[9] [d]
r0948[15] [ms]
r2130[15] [d]
Fault time
"removed"
r2109[0] [ms]
r2136[0] [d]
r2109[1] [ms]
r2136[1] [d]
r2109[7] [ms]
r2136[7] [d]
r2109[56] [ms]
r2136[56] [d]
r2109[57] [ms]
r2136[57] [d]
r2109[63] [ms]
r2136[63] [d]
r2109[8] [ms]
r2136[8] [d]
r2109[9] [ms]
r2136[9] [d]
r2109[15] [ms]
r2136[15] [d]
1
p2147 (CU) = 1
POWER ON
Fault times
Faults Acknowledging
<2>
Control Unit Fault Present
r3114.10
r3115[63]
r3115[57]
r3115[56]
r3115[15]
r3115[9]
r3115[8]
r3115[7]
r3115[1]
r3115[0]
Fault Drive
Object
initiating
r3131
Fault value act
r3120[63]
r3120[57]
r3120[56]
r3120[15]
r3120[9]
r3120[8]
r3120[7]
r3120[1]
r3120[0]
Component
number
fault
r3122[63]
r3122[57]
r3122[56]
r3122[15]
r3122[9]
r3122[8]
r3122[7]
r3122[1]
r3122[0]
Diagnostic
attribute
fault
Fault goes
Fault comes
Fault case
acknowl.
r0944
Fault buffer
change
r0945[57]
r0947[57]
r0945[7]
r0947[7]
r3132
Comp_no act
System runtime
r2114 [ms]
<1>
[2546.1]
Fault gone/can be acknowledged
r2139.15
r2139 ZSW fault/alarm 1
Fault present
r0196.10
Fault gone/can be acknowledgedr0196.15
r0196[0...255] Top comp stat